AKO AKO-156332 Manuel - Sayfa 4

Sıcaklık Kontrolörü AKO AKO-156332 için çevrimiçi göz atın veya pdf Manuel indirin. AKO AKO-156332 6 sayfaları. Optical and acoustic alarm and emergency lighting for low temperature or controlled atmosphere cold stores
Ayrıca AKO AKO-156332 için: Manuel (4 sayfalar)

AKO AKO-156332 Manuel
If the cable supplied for connecting the push button is not used, use a V3V3-F type cable with three 0,5 mm2 wires and
a minimum resistance of 300/500 V. The maximum distance is 100 m.
Any of the push buttons may be replaced by a volt-free contact, after first switching off the wiring monitoring function on
the input in question (see section 3.5) and connecting it as shown in the sketch.
POWER SUPPLY CONNECTION
AND ALARM OUTPUT
8A
1
2
3
4
5
C
NC
NO
Input
Output
230 VAC
ALARM
Connection detail
volt-free contact
IMPORTANT: To avoid false alarms during the push button wiring process, always follow this order:
Set all the S1 microswitches in the up position > Connect the 3 cables, beginning with the GND cable > Set
the S1 microswitches in their correct position (see next section).
3.5 Configuration
Monitoring the wiring
Set the wiring monitoring function on or off in each of the inputs (see
page 7).
If a volt-free contact is used on any of the inputs, set the microswitch
in the up position, which will switch the wiring monitoring off.
MODBUS address
Determine the MODBUS address of the alarm during commissioning.
This address may be changed later by software, in which case the
function of this microswitch will be cancelled.
Check correct operation of the alarm after it has been configured.
PUSH BUTTON CONNECTION
Input 1
Input
Input
Input
2
3
6
7
8
9 10
11
12
13
14
15
4
MODBUS
16
17 18 19 20
(RS-485)
PUSH BUTTON 4
PUSH BUTTON 3
S1
1 2 3 4
Input No.
S2
ON
1
2
PUSH BUTTON
GND
+12Vcc
PUSH BUTTON 2
PUSH BUTTON 1
Function Off
Function On
Micro
Address
96 (Decimal)
97 (Decimal)
98 (Decimal)
99 (Decimal)
11