AKO 55724 Kullanıcı Kılavuzu - Sayfa 7
Güvenlik Sistemi AKO 55724 için çevrimiçi göz atın veya pdf Kullanıcı Kılavuzu indirin. AKO 55724 16 sayfaları. Gas leak detection alarm
Wiring
The wiring between the transmitter / detector / push-button and the station should NEVER be installed in a
conduit alongside power, control or supply cables.
Always disconnect the power supply to carry out wiring.
For disconnection, the power supply circuit must be equipped with a switch of at least 2 A, 230 V, located near
the device. The power supply cable will be H05VV-F or NYM 1x16/3. The section to be used will depend on
current local regulations, but should never be less than 1.5 mm .
Cables for wiring the relay contact should have the relevant section for the device to be connected
The 120 / 230 V~ wiring area must be kept clear of any other external element.
Certain international standards indicate that alarm power supply should originate from a different circuit to
that used for the refrigeration and ventilation system. Be sure to comply with current local regulations.
AKO-55624
D
Vac
100 - 240 V~
50/60 Hz
A
RS485
Remote
mute
B
Input 1
Input 1
Pre-alarm jumper
Pre-alarm
disabled
Pre-alarm
enabled
Gas Fail
NO
C
NC
Gas
system
failure
Remote
Set Hold
RY2
RY3
NC
C
NO
NC
C
NO
Gas
Gas
Pre-Alarm
Alarm
2
A
Gas transmitter AKO-575xxx
Input x
Input x
7
5572H402 Ed.03
B
D
15V
S
GND
Gas detector AKO-5761x
15V
S
GND