Advanced configuration
The parameters are grouped into 6 sections depending on their function. To access it, press the
Temperature values are expressed in ºC. (Equivalent temperature in ºF)
If the access code is activated, a 2 digit code is requested, if the code entered is incorrect the unit will not enter programming mode.
After 20 seconds with no key being pressed, the equipment will return to the previous level. If you are on level 3, the changes will not be saved.
REGULATION AND CONTROL
Description
SP
Temperature Adjustment (Set Point)
rE
C0
Calibrating probe 1 (Offset)
C1
Probe 1 differential (Histeresis)
Upper blocking of the set point
C2
(cannot be set above this value)
Lower blocking of the set point
C3
(cannot be set below this value)
Type of delay for protection of the compressor
C4
0=OFF/ON (since the last disconnection);
1=OFF-ON/ON-OFF (since the last shut-down /start-up)
Protection delay time
C5
(value of the option selected in parameter C4)
Status of COOL relay with probe fault
C6
0=OFF; 1=ON; 2=Average based on last 24 hours prior to probe fault;
3=ON-OFF as prog. C7 and C8
Time relay ON in case of faulty probe
C7
(If C7=0 and C8¹0, the relay will always be OFF deenergised)
Time relay OFF in case of fault of probe 1
C8
(If C8=0 y C7¹0, the relay will always be ON energised)
Idle time of the digital input for the change Set Point function to be
C11
activated (Only if P10 or P11 =1) (0=OFF)
Variation of the set point (SP) when the change set point function
C12
is active. (SP+C12 £ C2) (0= disabled)
EP
Exit to Level 1
DEFROST CONTROL
Description
d0
Defrost frequency (Time between two starts)
dEF
d1
Maximum defrost duration (0=defrost deactivated)
Type of message during defrost:
d2
0=Current temperature; 1=Temperature at start of defrost;
2=Display dEF message
Maximum duration of message
d3
(Time added at the end of the defrost process)
d4
Defrost end temperature (probe 2) (If P4 ¹ 1)
Defrost on equipment start-up
d5
0=NO, First defrost as per d0
1=YES, First defrost as per d6
d6
Defrost start delay on equipment start-up
Calculated time between defrost period :
d8
0=Total actual time; 1 =Sum of times the compressor is on
Drip time at end of defrost
d9
(compressor and fans off) (if P4 ¹ 1)
EP
Exit to Level 1
FAN CONTROL
Description
F0 Fan shut-down temperature as per probe 2 (if P4 ¹ 1)
FAn
F1 Probe 2 differential (If P4 ¹ 1)
F2 Stop fans when stopping compressor 0=No, 1=Yes
F3 Fan status during defrost: 0=Parados; 1=En marcha
Starting delay after defrost (if F3=0)
F4
Will only operate if it is higher than d9
EP Exit to Level 1
Technical specifications
Rated voltage Un .............................................................400 V~ ±10 % 50/60 Hz ±5 %
Rated voltage Ue .............................................................230 V~ ±10 % 50/60 Hz ±5 %
Maximum nominal input current................................................................................32 A
Short-circuit current at the connection point ..............................................................6 kV
Probe temperature range ...................................................................–45.0 ºC to 99.9 ºC
Resolution, setting and differential..........................................................................0.1 ºC
Thermometric precision ..........................................................................................± 1 ºC
Precision of the NTC probe at 25 ºC ....................................................................± 0.4 ºC
Input for NTC probe .......................................................................................AKO-14901
Maximum input power in the operation ...................................................................30 VA
Working ambient temperature ....................................................................-5 ºC to 40 ºC
Value Min. Def. Max.
0.0
ºC / ºF
-45
99
A0 Configuration of temperature alarms : 0=Relative to
AL
ºC / ºF
-20.0
0.0
20.0
A1 Maximum alarm probe 1 (must be greater than SP)
0.1
2.0
20.0
A2 Minimum alarm probe 1 (must be greater than SP)
ºC / ºF
A3 Temperature alarm delay during start-up
ºC / ºF
C3
99
99
A4 Temperature alarm delay after completion of a defrost
ºC / ºF
-45
-45
C2
A5 Temperature alarm delay after reaching the value of A1 or A2
A6 External alarm delay when receiving digital input signal (P10 or P11=2 or 3)
0
0
1
A7
A8 Show warning if defrost is terminated by time-out 0=No, 1=Yes
min.
0
0
120
A10 Temperature Alarm Differential (A1 and A2)
A12 Door open alarm delay (if P10 or P11=1)
0
2
3
EP
min.
0
10
120
P1
CnF
min.
0
5
120
P2
h.
0
0
24
P3
ºC / ºF
C3-SP 0.0 C2-SP
P4
P7
Value Min. Def. Max.
0
6
96
P8
min.
0
15
255
P10
0
2
2
min.
0
5
255
P11
ºC / ºF
-45
8.0
99.0
P12
0
0
1
P13
min.
0
0
255
P14
0
0
1
P15 Maximum pump down time (0=Disabled)
min.
0
1
255
P23 Stop evaporator fans and compressor on opening door 0=No 1=Yes
P24 Start up delay for fans and compressor with door open
P26 Pump Down 0=Without pump down 1=With pump down
Value Min. Def. Max.
EP
(ºC/ºF)
-45
45
99.0
(ºC/ºF)
0.1
2.0
20.0
L5
tid
0
1
1
PU Control board software version(Information)
0
0
1
Pr
(min.)
0
3
99
PUd Display board software (Information)
Prd Display board software review (Information)
EP
Storage ambient temperature...................................................................–30 ºC to 70 ºC
Overvoltage category ..............................................................................II s/ EN 61439-1
Degree of pollution .................................................................................II s/ EN 61439-1
Degree of protection .................................................................................................IP65
Dimensions AKO-17632 / 17635 / 15720 / 15721......400(An) x 300(Al) x 165(P) mm
Double isolation between power supply, secondary circuit and relay output.
Type of assembly .........................................................................................Fixed internal
Programming key compatible .....................................................................AKO-D14918
Encapsulated assembly
2
key for 10 seconds. The Def. column shows factory-set default parameters.
ALARM CONTROL
Description
Deactivation delay of the external alarm when the signal of the digital input
disappears (P10 or P11=2 or 3)
Exit to Level 1
GENERAL STATUS
Description
Delay of all functions on receiving electrical power
Función del código de acceso (password)
0= Inactivo; 1= Bloqueo acceso a parámetros; 2= Bloqueo del teclado
Configures the default factory settings
0= No changes 1=Return to default settings
Selection of type of inputs
1=Sonda S1 2=Sondas S1 + S2
Temperature display mode
0=Integers in ºC
1=One decimal in ºC
2=Integers in ºF
3=One decimal in ºF
Probe to be displayed (as per parameter P4)
0=visualization of all the probes in sequence;
1=Probe 1 2=Probe
Configuring digital input 1
0=
Off
1= Door contact
2= External alarm
3= Severe external alarm
Configuring digital input 2
0=
Off
1= Door contact
2= External alarm
3= Severe external alarm
Digital input polarity 1
0=Energised on closed contact, 1=Energised on open contact
Digital input polarity 2
0=Energised on closed contact, 1=Energised on open contact
Maximum start-up time after pump down
(Values between 1 and 9 seconds are not accepted) (0=Disabled)
Exit to Level 1
ACCESS CONTROL AND INFORMATION (tid)
Description
Access code (Password)
Control board software review (Information)
Exit to Level 1
AKO-17633 / 17634 / 17636 / 17637......500(An) x 400(Al) x 175(P) mm
GB
1763H202 Ed.02
Value Min. Def. Max.
0
1
1
(ºC/ºF)
A2
99,0
99,0
(ºC/ºF)
-45
-45
A1
(min.)
0
0
120
(min.)
0
0
99
(min.)
0
30
99
(min.)
0
0
120
(min.)
0
0
120
0
0
1
(ºC/ºF)
0,1
1,0
20,0
(min.)
0
10
120
Value Min. Def. Max.
(min.)
0
0
255
0
0
2
0
0
1
1
1
2
0
1
3
0
1
2
0
0
5
0
0
5
0
1
1
0
1
1
(seg.)
0
0
120
(min.)
0
0
15
0
0
1
(min.)
0
0
999
0
1
1
Value Min. Def. Max.
0
0
99
-
-
-
-