INSTALLATION AND USER INSTRUCTIONS FOR THE:
Digital, 12 V, two-relay, panel mounted thermostat
for Pt 100 probes, up to 600ºC
AKO-14721
GENERAL DESCRIPTION:
Panel-mounted electronic thermostat, suitable for display, control and regulation of heat or cold genera-
tors.
VERSION:
MODEL
FUNCTION
MOUNTING
RELAYS
1: 8A cos ϕ =1 (SPDT)
AKO-14721 Thermostat
Panel-mounted
2: 8A cos ϕ =1 (SPDT)
TECHNICAL SPECIFICATIONS:
Temperature range: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -50ºC to 600ºC
Pt 100 probe entry: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ref. AKO-15585, AKO-71726, AKO-71727
Controller accuracy: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ambient working temperature:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5ºC to 50ºC
Ambient storage temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -30ºC to 70ºC
-with independent mounting
-with characteristic of automatic operation action, Type 1.B
Control device classification:
-to be used in clean situation
INSTALLATION:
Thermostat:
The thermostat must be installed in a place away from vibrations, water and corrosive gas and where the
ambient temperature is within the range in the technical specifications.
For protection level IP65, the joint between the device and the surrounding of the panel space where it is
installed must be properly made.
Probe:
For correct readings, the probe must be installed in a place free of thermal
effects other than the temperature to be measured or controlled.
This diagram shows how the probe must be connected:
Connections:
Connect plugging terminals according to the rating plate diagram.
The probe and its corresponding cable should NEVER be installed in ducting along with mains, control
or power supply wiring, probe cables
max.
can be extended and no deviation
18 mm
3
will appear.
1
Fastening:
To fix the unit, place the fasteners 1
over the sliders 2 as shown in the figu-
re. Move the fasteners in the direction
of the arrow. By pressing tab 3, the
fasteners may be moved in the oppo-
site direction to the arrow.
61,5
FRONT PANELS FUNCTIONS:
LED PR
Functions:
PR
UP key
LED 1
1
During programming, increases
LED 2
2
the figure being displayed.
DOWN key
During programming, lowers
the figure being displayed.
Holding it down for 5 seconds brings up the temperature adjustment menu.
+
Held down simultaneously for 10 seconds brings up the programming menu.
+
Held down simultaneously enters the new value.
Indicator LEDs:
LED 1
constant: Shows relay 1 is on.
flashing: Means relay 1 should be on according to the temperature detected by the probe,
but is not, owing to a programming condition.
LED 2
constant: Shows relay 2 is on.
flashing: Means relay 2 should be on according to the temperature detected by the probe,
but is not, owing to a programming condition.
LED PR
flashing: Programming set point or parameters.
TEMPERATURE SET POINT:
The default (factory) setting for
SET POINTS 1 and 2 are 0ºC
5 Sec.
SELECTION
TEMPERATURE
PRESENT
DISPLAY
SETTING
SP1= Set Point for R1
SP2= Set Point for R2
PRESENT
SETTING
1
- Hold the
key down for 5 seconds. This opens the SP1 or SP2 setting menu (the PR led will flash).
- Press the
or
- Press the
+
®
- Press the
or
PUBLICACIÓN
- Press the
+
the temperature again and the PR led stops flashing.
1472H100
NOTE: If no key is pressed for 30 seconds during any of these steps, the controller automatically returns
Edición 02
to temperature display, neither of the SET POINTS being changed.
RELAY CONTROL AND OPERATING MODES
P00=0 ON-OFF Switching
ON
POWER SUPPLY
RELAY 1
12V ,
15%, 173 mA
OFF
SP1
Temp.
OFF
0,5ºC
ON
RELAY 2
OFF
SP2
Temp.
OFF
P00=1 Neutral Zone
10 11 12
Pt100
PROGRAMMING:
2
Parameters should only be programmed or chenged by personnel familiar with the operation of the
apparatus and its possibilities where applied.
Programming parameters:
Level 1:
-Hold the
+
keys down simultaneously for 10 seconds. The PR led will flash and the first parame-
PANEL CUT-OUT
ter, "P00", will be shown on the display.
-Press the
or
-When the final parameter EP is on the display, press the
70,5
return to the temperature display and the PR led will stop flashing.
Level 2:
UP key
-To see the current value of any parameter, find the one you want and press the
ously. When it is on display, you can change it with the
-Press the
+
keys simultaneously to set the new value. When you do this, the programming will return
to level 1 (parameters).
PRG
ºC
NOTE: If no key is pressed for 30 seconds during any of these steps, the controller automatically returns
SET
to temperature display, none of the parameter values being changed.
DOWN key
TEMPERATURE
INDICATION
NEW
SETTING
NEW
SETTING
key to select SET POINT 1 or SET POINT 2.
keys simultaneously to show the setting you want to change.
keys to change the SET POINT to the figure you want.
keys simultaneously to enter the new figure. When you do this, the display shows
COLD operation P01=0
HEAT operation P01=1
C11>0
C11>0
C11<0
ON
OFF
SP1 + C11
SP1 - C11
SP1
SP1
SP1 + C11
SP1 - C11
Temp.
Temp.
Temp.
Temp.
Temp.
ON
OFF
ON
ON
OFF
COLD operation P02=0
HEAT operation P02=1
C12>0
C12<0
C12>0
ON
OFF
SP2 + C12
SP2 - C12
SP2
SP2
SP2 + C12
SP2 - C12
Temp.
Temp.
Temp.
Temp.
Temp.
ON
OFF
ON
ON
OFF
ON
RELAY 1
OFF
ON
RELAY 2
OFF
SP1 - C15
SP1
SP1 + C15
key to change to the next parameter or previous parameter, respectively.
+
keys simultaneously, the controller will
+
or
keys.
LEVEL 1
LEVEL 2
PARAMETERS
VALUES
10 Sec.
CURRENT VALUE
NEW VALUE
PROGRAMMING
EXIT
2
DESCRIPTION OF PARAMETERS:
For Set Point programming, see TEMPERATURE SET POINT.
The figures in the DEF column are the factory settings.
PARAMETER
P00
Operating mode
Selection 0= ON-OFF Switching.
See operating modes.
Set points can be programmed separately for each relay.
Selection 1 = neutral zone.
See operating modes.
P01
Operation (cold/heat) of relay 1
Selection 0 = Cold
Selection 1 = Heat
C11<0
P02
Operation (cold/heat) of relay 2
Selection 0 = Cold
Selection 1 = Heat
P07
Resolution for temperature display.
SP1
0=0,1ºC between -50,0 and +99,9ºC rest of the range 1ºC
Temp.
Temp.
1= 1ºC for the complete range.
ON
OFF
P3
Return to original parameters
1 sets all parameters in the device to the values in the DEF. VALUE column of
this table, then exits programming immediately.
C12<0
C0
Probe calibration (offset)
Increases or decreases the correction to the temperature detected by the ther-
mostat in order to adjust the probe to real temperature.
C11
R1 Differential
SP2
Increases or decreases the temperature from that indicated by SET POINT 1 (SP1)
for R1 to be switched on.
Temp.
Temp.
See relay 1 operating in ON-OFF switching mode.
ON
OFF
C12
R2 Differential
Increase or decreases the temperature from that indicated by SET POINT 2 (SP2)
for R2 to be switched on.
See relay 2 operating in ON-OFF switching mode.
Neutral zone value
C15
Increases/decreases the temperature above or below SET POINT 1 for relays R1
and R2 to act.
See Neutral Zone operating.
C21
Maximum limit for R1 SET POINT
Relay 1's SET POINT cannot be established above this figure, the alarm AH being
produced if the temperature is above the value of C21 and C22.
C22
Maximum limit for R2 SET POINT
Relay 2's SET POINT cannot be established above this figure, the alarm AH being
produced if the temperature is above the value of C21 and C22.
C31
Minimum limit for R1 SET POINT
Relay 1's SET POINT cannot be established below this figure, the alarm AL being
produced if the temperature is less than the value of C21 and C22.
C32
Minimum limit for R2 SET POINT
Relay 2's SET POINT cannot be established below this figure, the alarm AL being
produced if the temperature is less than the value of C21 and C22.
C51
Relay R1 Triggering Delay
Delay for R1 being triggered after the temperature commands its activation.
C52
Relay R2 Triggering Delay
Delay for R2 being triggered after the temperature commands its activation.
C61
R1 status when the probe has failed
0=off
1=on
keys simultane-
C62
R2 status when the probe has failed
0=off
1=on
EP
Exit Programming
OPERATING MESSAGES:
DISPLAY
STATE
E1
Steady
Flashing with
AH
temperature
Flashing with
AL
temperature
EE
Steady
MAINTENANCE:
Clean the surface of the controller with a smooth cloth, soap and water. Do not use abrasive detergents,
petrol, alcohol or solvents.
WARNINGS:
Using this unit without heeding the manufacturer's instructions may change its safety requirements.
AKO Electromecànica S.A.L. Apartado de Correos, 5. 08800 Vilanova i la Geltrú (Spain)
351472100 Rev. 01 2000
D.L.: B-33.685-00
DEF.
RANGE
DESCRIPTION
VALUE
MIN.
MAX.
0
1
0
0
1
1
0
1
1
0
0
1
-
1
-
-20ºC
20ºC
0ºC
-650ºC +650ºC
2ºC
-650ºC +650ºC
2ºC
0ºC
325ºC
2ºC
xxxºC
600ºC
600ºC
xxxºC
600ºC
600ºC
-50ºC
xxxºC
-50ºC
-50ºC
xxxºC
-50ºC
0 min. 99 min.
0 min.
0 min. 99 min. 0 min.
0
1
0
0
1
0
DESCRIPTION
Probe short circuited, circuit open >614ºC or <-60.6ºC
Temperature above the maximum limit values set in C21 and C22.
Temperature below the minimum limit values set in C31 and C32.
Memory failure
3