INSTALLATION GUIDE
TERMINALS
Location
Illustration
DS0119 rev 40
©2018 Cylon
Terminal
Numbers
Universal Inputs
1 ... 12
When input is configured as Digital:
LED Off: open circuit or logic 'off'
LED On: logic 'on'
When input is configured as Resistor/thermistor:
LED Off: valid resistance connected (Note: 0 Ω is counted as valid)
LED Slow blink: resistor/thermistor not connected
When input is configured as Analog:
LED intensity is modulated by the analog signal
When the LED is blinking:
Fast blink indicates error condition
Two short flashes followed by a value* indicates the input is in an override state (overridden
HD
CXpro
by
).
*Note: The LED intensity illustrates the value measured at the input terminals. The flash
indicates that this value has been overridden.
UniPuts™ + Relay
25 ... 38
TM
When a Uniput
channel is configured as an input, the LED signals are identical to Universal Inputs
above. When configured as an output the following apply:
When output is configured as Digital:
LED Off: open circuit or logic 'off'
LED On: logic 'on'
When output is configured as Analog:
LED intensity is modulated by the analog signal
When the LED is blinking:
Fast blink indicates error condition
Two short flashes followed by a value indicates the output is in an override state
(overridden by
Digital Inputs
(FLX16DI
only)
1 ... 12,
LED Off: open circuit or logic 'off'
26 ... 37
LED On: logic 'on'
When the LED is blinking:
Fast blink indicates error condition
Two short flashes followed by a value indicates the output is in an override state
(overridden by
93, 94
24 V AC Power
13 ... 15
Auxiliary Power: 18 V DC output on 2 terminals, 60 mA total
95, 96
BACnet® MS/TP Port (RS-485) screw terminal
MS/TP subnet terminator switch is located beside the port. If the switch is towards the
termination is in and if the switch is towards the
39 ... 42
UCU Room Display / CBT-STAT Port
The CBT-STAT bus Terminator Switch is located beside the port. If the switch is towards the
termination is in and if the switch is towards the
43, 44
Modbus RTU
The Modbus Terminator Switch is located beside the port. If the switch is towards the
termination is in and if the switch is towards the