MAN REALS: This amber LED will glow when manual release switch is pressed to
release the gas.
ABORT: This amber LED will glow when abort switch is pressed to stop gas floating.
Disable: This amber LED will glow when disable switch is pressed to disable panels
operations.
GAS DISCHARGED: This amber LED will glow when the Gas in the cylinder starts
flowing through the discharge pipe.
SOV Operated: This amber LED will glow when timer counting is over and 24VDC
supply is on at SOV line.
SOV line open: This amber LED will glow when the continuity of the actuator valve line
is beaked.
CONTROLS:
RESET Key: This key is used to reset the entire system. While in reset condition, all
detector loop voltages are cut off up to 2 seconds for Detector and MCP become reset and
then voltages are put ON to the loop.
Note: We strongly recommend to avoid to do the RESET unless there is fire in the zone.
SILENCE Key: While in the faults condition, when it is pressed, the local buzzer will be
silenced. During in fire condition, the SILENCE Key press mutes the external hooters
and silence LED Glows.
LAMP TEST Key: As long as we are keeping this key in hold condition, all the LED's
will glow to identify whether all the LED's are in working condition or not.
AUTO/MANUAL LED: This toggle switch is used to select the operating mode of the
panel. By default AUTO mode is selected.
MANUAL RELEAS: This switch is used to release the gas manually in manual mode of
the panel only. There is no ABORT OR TIMER facility for release of the gas in manual
release mode.
ABORT: This switch is used to stop the Gas floating. When ever this switch is on, timer
will stop counting, gas discharge valve will not operate. This switch will turn off after the
panel is reset. Abort switch will not operate in manual operation mode of the panel.
DISABLE: This switch is used to disable the gas floating part of the panel. In this mode
the panel will only function as simple fire alarm control panel, i.e. sensors will sense fire
and the sounder will starts sounding, but no gas discharge section will activate.