MODEL CXLdp HIGH ACCURACY
DIFFERENTIAL PRESSURE TRANSDUCER
INSTALLATION & MAINTENANCE SHEET
Set Up:
Note: For best immunity from EMI the pressure
connection fittings on the CXLdp High Accuracy
should not be grounded.
The transmitters are calibrated at the factory in the
vertical position. Mounting in the horizontal posi-
tion can cause a zero shift of as much as ±1% F.S.
in ranges below 1 W dp. Any minor zero offset can
be minimized using the zero adjust potentiometer
located on the front, left side of the instrument.
To find true zero differential pressure, pneumati-
cally connect the high and low pressure connec-
tions together using the tubing provided with the
transmitter. The barbed connection accept
⁄
˝ I.D. tubing.
1
8
(see Figure 5)
Figure 5
When
⁄
NPT fe-
1
8
male brass fittings
are used, do not
exceed 60 inch-
pound torque force
on female NPT fit-
ting.
When connecting
to the NPT fittings,
do not apply torque
Figure 6
to the CXLdp High
Accuracy fitting. Use
a
⁄
˝ wrench to hold
9
1 6
the CXLdp. (see
Figure 6)
Zero potentiometer
adjustment requires
using a
⁄
˝ or 2.5
3
3 2
mm slotted or
phillips screwdriver. The tubing should remain in
place until the transmitter is to be connected to the
BCS tubing system.
(see Figure 7)
© 2014 Ashcroft Inc. 250 East Main Street 06614, Tel: 203-378-8281 • Fax: 203-378-0499, All specifications are subject to change without notice.
All sales subject to standard terms and conditions. www.ashcroft.com All rights reserved. I&M011-10137 11/14
Zero and Span Potentiometers
Figure 7
ZERO
Zero adjust
potentiometer
Routine Maintenance:
The CXLdp High Accuracy is a very stable and
reliable transmitter incorporating a proven, micro-
machined silicon capacitive sensor and a new,
1
⁄
˝ O.D.
4
state-of-the-art application specific integrated
circuit (ASIC). All calibration and temperature com-
pensation functions are done with a microprocessor
and digital routines.
To troubleshoot or verify performance, it is recom-
mended to pneumatically connect the pressure
ports to each other and establish a zero offset
reading in the as-installed position. Adjusting zero
will not affect span calibration.
Adjusting span should only be attempted when a
high accuracy pressure standard and high quality
electrical meter are able to be used.
DIN Rail Transmitter Removal:
In order to remove the transmitter when it is installed
on a DIN rail, it is necessary to first unplug the wiring
terminal block from the transmitter.
Insert a small slot-
ted screwdriver into
the black plastic
clip extending
slightly below the
transmitter case.
(see Figure 8)
Next, raise the
screwdriver handle
up thereby forcing
the spring clip down.
If questions or concerns need to be addressed, our
Low Pressure Product Manager or Engineering
Personnel can be contacted at (203) 378-8281 or
visit our website at www.ashcroft.com.
SPAN
Span adjust
potentiometer
.56
Figure 8
GENERAL DIMENSIONS FOR
MODEL CXLDP HIGH ACCURACY (in inches)
MB2
⁄
˝ BARB FITTINGS
1
4
"B2" 1/4 BARB FITTINGS
1.45
ÿ .20
POWER
HI
LO
2.90
3.33
ZERO
SPAN
ÿ .16
1.89
F01
⁄
NPT FEMALE FITTINGS
1
8
"01" 1/8 FEMALE NPT FITTINGS
1.45
POWER
HI
LO
2.90
3.33
ZERO
SPAN
1.89
ASSEMBLED WITH 101A213-01
CONDUIT KIT
ASSEMBLED WITH 101A213-01 CONDUIT KIT
4.85
4.85
2.06
2.06
R R .88 .88
.78 .78
.37
1.32
HOUSING TABS (2)
.37
1.32