A-H To enter span analog output reference corresponding to 5 V
analog output.
This application does not use the analog output.
Step
100.0 is displayed. That is the transmitter default analog output at
5
100% FS (5 V at 1.00 IWC).
Press and release MODE button to select and move to the next step.
GC30 Transmitter Switch Set Point and Dead Band Set Up Method:
Press and hold MODE button less than three seconds to get into program
mode.
Press UP or Down arrow to make changes.
Press and release MODE button to select changes and to move to the next
step.
Continue to Step-1 after once in program mode.
Press and hold MODE button for more than three seconds to return to
measuring mode.
A-1 To enter output 1 switch audible alarm set point when
differential pressure reaches .500 IWC.
Step
Press UP or Down until .500 is displayed.
1
Press and release MODE button to select and move to the next step.
b-1 To enter output 1 switch dead band.
Step
Set dead band to .300 IWC to deactivate switch at .200 IWC.
2
Press UP or Down until .300 is displayed.
Press and release MODE button to select and move to the next step.
On1 To delay output 1 switch turn on.
Step
Delay output 1 switch turn on shall not be used for this application.
3
Press Up or Down arrow until 0.00 is displayed.
Press and release MODE button to select and move to the next step.