Mounting - Srew fixing at ND 5014/120
Screws are not included in the delivery !
Mounting instructions for srew fixing
To high forces applied during installation can damage the transformer on
the mounting foots.
The mounting foots are only designed to fix the transformer. Forces that are
applied to the CT by the conductors can only be supported within limitations.
When installing the CT, the conductors should be lead free through the
transformer and should later stay in that position.
Wiring Information Residual Current Monitor
The hinged cover protects the push-in terminal block and avoids unin-
tended disconnection of the wiring
The push-in terminal block provides easy mounting
Stripping length:
10 mm
Connecting capacity:
0.2 .... 2.5 mm
For further details see separate data sheet ND 5014