4.2 Solar PV connections
REhub accepts input voltages between 0V to 90V. It can start charging the batteries when
the input voltage is above the battery voltage. Keep the connection ready. Close the
connections when you are ready to POWER Up.
4.2.1 Serial connection of Solar PV string
must be strictly followed.
To get the optimum Voltage, the solar modules shall be connected in series to form a
string having the desired voltage. The optimum operating voltage of the module string
(Vmpp) must always be above the battery Voltage.
To establish the minimum number of PV modules to be connected in series in the same
string, the max voltage of the battery must be multiplied by 1.1 and divided by the
modules Vmpp voltage.
For example, for a 24V system with a lead-acid battery with maximum Voltage of 30 V
and using PV panels with 17V Vmpp. 30*1.1/17=1.94.
The result must be rounded up to the higher value (i.e. 2 modules - of 17 Vmpp - in series
for the above example is the MINIMUM number of panels required for operation).
4.2.2 Maximum Panels in Series
The open-circuit voltage of the string must be lower than 90V under any temperature and
irradiation conditions.
To establish the maximum numbers of the PV modules connected in series in the
same string, use the following formula: 90V/(Voc). (Example: 90/(22)=4.09). The result
must be rounded down to the lower value (i.e. 4 modules - of 22 Voc - in series for the
above example).
There can be thus 4 PV modules in series of the mentioned model for a 24V system as per
this example.
Table 4 gives an idea of the possible arrangements for common panels according to the
number of cells or their type.
Note that CIS or other forms of THIN film PV modules cannot be connected to REhub
unless their Voc is <90V.
6
Comment
Connect existing Mains-in Plug of the Inverter
to this socket
Connect Amberlink
separately) to this port.
Use this switch to Select the way in which Mains
input to the Inverter is controlled.
Ver 7.0
©
(available for purchase
Table 4 : Maximum panels in a
string
REhub can operate at a much
higher PV voltage compared
to
the
Battery
Voltage. It is therefore not
necessary to match the PV
panel voltage to the Battery
Voltage. However, the name
plate limits of the PV input
User Manual
system