Ambirad DR 160 Інформація для користувача, інструкції з монтажу та обслуговування - Сторінка 6
Переглянути онлайн або завантажити pdf Інформація для користувача, інструкції з монтажу та обслуговування для Газовий обігрівач Ambirad DR 160. Ambirad DR 160 15 сторінок. Radiant gas heaters
GAS SUPPLY
The gas supply to the heater must terminate in an isolation cock. This will allow the heater to be disconnected for
maintenance or repair.
All pipework must be supported and installed in accordance with the regulations listed on page 4 and to provide the
operating gas pressure and volume for the appliance. Pipes of a smaller size than the heater inlet gas connection
must not be used.
The final connection is made to the heater gas valve. This has an Rp 1/2" ISO 7 thread (1/2" B.S.P. internal thread).
A flexible metallic hose conforming to B.S. 6501: Part 1: 1991 (minimum specification type B Class 1) may be used
for this purpose. This must be kept clear of the flue products opening at the top of the heater.
Take care when making the final connection to the gas valve not to apply excessive turning force to the gas valve.
The valve inlet may be held using a 40mm spanner.
GAS PRESSURE
The following information is valid for heaters supplied in the UK and Ireland using either natural gas or propane fuel.
Please check heater data plate and packaging to verify fuel type. ( Information on converting heaters for use in other
European countries is given in a section at the end of this manual. See page 11.)
MAXIMUM INLET GAS PRESSURE -
The gas pressure governor has been factory pre-set to give the following heater operating pressures:
15 mbar for Natural gas (G20)
25 mbar for Propane (G31).
ELECTRICAL INSTALLATION
THIS APPLIANCE MUST BE EARTHED
A 220/24OV 50Hz single phase supply is required.
All wiring must comply with l.E.E. and local authority recommendations. The wires in the mains lead used on this
appliance are coloured in accordance with the following code :
Green and Yellow
Blue
Brown
The method of connection to the electricity supply must facilitate complete isolation and should preferably be made
via a fused double pole isolator having a contact separation of at least 3mm in all poles and supplying the appliance
only. Alternative connection may be made via fused three pin plug and unswitched, shuttered socket both complying
with the requirements of B.S. 1363.
Ensure that Live, neutral and earth are connected correctly as the flame detection circuit will not operate correctly
if the polarity of the supply is reversed.
HEATER CONTROL WIRING
1
L
220/240V
SUPPLY
N
E
6
20 mbar for Natural Gas
37 mbar for Propane
Earth
Neutral
Live
P16 B GAS CONTROLLER
2
3
4
5
6
7
Brown
Blue
Green/Yellow
Brown
Grey
8
9
10
Green
E
N
L
IGNITION ELECTRODE
FLAME SENSING ELECTRODE
Green/Yellow
SIT GAS
Blue
VALVE
Brown
Black