Ekinex KNX EK-ED2-TP-RW Посібник із швидкого старту - Сторінка 4

Переглянути онлайн або завантажити pdf Посібник із швидкого старту для Контролер Ekinex KNX EK-ED2-TP-RW. Ekinex KNX EK-ED2-TP-RW 5 сторінок. Pushbutton

!
Warning! In order to supply the KNX bus lines use
only KNX bus power supplies (e.g. ekinex EK-AB1-
TP or EK-AG1-TP). The use of other power supplies
can compromise the communication and damage
the devices connected to the bus.
Bus
KNX
-
+

Configuration and commissioning

Configuration and commissioning of the device require
the use of the ETS
(Engineering Tool Software) program
®
V4 or later releases. These activities must be carried out
according to the design of the building automation system
done by a qualified planner.
i
Note. The configuration and commissioning of KNX
devices require specialized skills. To acquire these
skills, you should attend the workshops at KNX cer-
tified training centers.
Product
Application program
code
(## = release)
EK-ED2-TP
APEKED2TP##.knxprod
EK-E32-TP
APEKED2TP##.knxpro
Configuration
For the configuration of the device parameters the corre-
sponding application program or the whole ekinex
duct database must be loaded in the ETS program. For
detailed information on configuration options, refer to the
application manual of the device available on the website
www.ekinex.com.
Commissioning
For commissioning the device the following activities are
required:
• make the electrical connections as described above;
• turn on the bus power supply;
• switch the device operation to the programming mode
as described in the next table;
• download into the device the physical address and the
configuration with the ETS
At the end of the download the operation of the device
automatically returns to normal mode; in this mode the
programming LED (where available) and/or the LEDs of
the second color (for EK-ED2-TP-...) are turned off. Now
the bus device is programmed and ready for use.
Communica-
Group
tion objects
adresses
(nr. max)
(nr. max)
229
254
229
254
pro-
®
program.
®
Product
FW
code
version
04.xxx
and pre-
vious
from
05.xxx
to
06.018
EK-ED2-
TP
06.019
and
later
EK-E32-TP
All

Reset of the device

To reset the device:
• if the programming button is present, remove the con-
nection to the bus network by extracting the bus ter-
minal from its seat. Keeping the programming button
pressed, reinsert the bus terminal in its seat; the pro-
gramming LED flashes quickly. Release the program-
ming button and extract the clamp again; the reset has
been performed.
• If, on the other hand, the programming button is not
present, repeat the programming sequence by holding
down the buttons for about 10 seconds. The LEDs of
the second color first flash, then go off; the reset has
been performed.
!
Warning! The reset restores the device back to the
state of delivery from the factory. The address and
the value of the parameters set during configuration
will be lost.
4
Programming
Visual
sequence
feedback
P r o g r a m -
Pressing the pro-
ming
gramming button
on steady.
Simultaneous press
of the first and last
button on the left
All LEDs of
side for 5 seconds.
the second
color flash.
P r o g r a m -
ming LED (if
present) on
steady.
Simultaneous pres-
sing of the first but-
ton on the left side
and the last button
on the right side for
5 seconds.
All LEDs of
the second
color flash.
P r o g r a m -
Pressing the pro-
ming
gramming button
on steady.
LED
LED