Ekinex EK-GD1-DL-4-HV Посібник - Сторінка 5
Переглянути онлайн або завантажити pdf Посібник для Диммер. Ekinex EK-GD1-DL-4-HV. Ekinex EK-GD1-DL-4-HV 6 сторінок. Dali 2 90-230 vac 4-channels phase cut dimmers
Summary table of load types depending on the input power supply
TE = Trailing Edge
SYMBOL
Halogen or incandescent bulbs (230V ~ 50/60Hz)
Ferromagnetic transformers (Halogen bulbs at 12/24V
Electronic transformers (Halogen bulbs 12/24V ~
Dimmable LED lamps (230V ~ 50/60Hz)
Lamp power supplies LED (230V ~ 50/60Hz)
Energy saving lamps (ESL/CFL)
SYMBOL
Halogen or incandescent bulbs (230V ~ 50/60Hz)
Ferromagnetic transformers (Halogen bulbs at 12/24V
Electronic transformers (Halogen bulbs 12/24V ~
Dimmable LED lamps (230V ~ 50/60Hz)
Lamp power supplies LED (230V ~ 50/60Hz)
Energy saving lamps (ESL/CFL)
!
Warning! Never connect the transformer wi-
thout first having connected the load on the se-
condary, to avoid overvoltages that are destruc-
tive to the appliance.
@220 V 50/60 Hz
LOAD TYPE
~ 50/60Hz)
50/60Hz)
LED strip (230V ~ 50/60Hz)
@110 V 50/60 Hz
LOAD TYPE
~ 50/60Hz)
50/60Hz)
LED strip (230V ~ 50/60Hz)
MAX POWER
SINGLE
CHANNEL
CHANNELS
230 W
115 W
115 W
115 W
230 W
MAX POWER
SINGLE
CHANNEL
CHANNELS
110 W
55 W
55 W
55 W
110 W
5
MODE
CURVE
SUM OF
460 W
TE
Linear
Incompatible
330 W
TE
Logarithmic
330 W
TE
Logarithmic
330 W
TE
Logarithmic
Linear /
460 W
TE
logarithmic
Incompatible
MODE
CURVE
SUM OF
220 W
TE
Linear
Incompatible
110 W
TE
Logarithmic
110 W
TE
Logarithmic
110 W
TE
Logarithmic
Linear /
220 W
TE
logarithmic
Incompatible