power supply and the device.
Characteristics of the supply and LEDs terminal block
• Screw tightening of the conductors
• Power & LEDs wiring: 2. 5mm
ded – 30 - 12 AWG
• Power and LEDs stripping recommended approx.: 7.5
mm
• Max torque 0.5 Nm
Outputs
The length of the connection cables between the dimmer
and the LED module must be less than 10m; the cables
must be correctly dimensioned and they should be isola-
ted from every wiring or parts at not-SELV voltage. It is
preferable to use double insulated shielded and twisted
cables.
In case it is needed to connect the device and LED mo-
dules with cables longer than 10m, the installer must gua-
rantee the correct functioning of the system. In any case,
do not exceed 30m of the connection between the device
and the LED modules.
230 Vac
50-60 Hz
Dimmer LED
EK-GL1-DL
DC In: 12-48V
Imput: Push, 0/1-10V
Out: 4x max 5A
L N
+
12-48 Vdc
Installation scheme

Configuration and commissioning

Configuration and commissioning activities of the device
must be carried out according to the design of the building
automation system done by a qualified planner.
For commissioning the device the following activities are
required:
• make the electrical connections as indicated above;
• power up the bus;
• carry out the device addressing, which can be done in
three ways:
1.
by means of rotary selector switches (positioned be-
low the front cover);
2.
simplified method: by connecting one ballast at a
time, each one will get the address progressively
from 0 to 63;
solid – 1.5 mm
stran-
2
2
DALI
OUT
-
-
L2-
L3-
+
3.
random address allocation: by connecting all the bal-
lasts at the same time, each one will get a random
address.
Subsequently, the address configuration can be changed
by using an application for parameterization, for example
by downloading the ekinex CGEKBG1TP software to your
PC which allows to:
• configure the DALI system and define its parameters;
• set the DALI luminaires (groups, scenarios, IDs, etc.);
• test the communication on the DALI bus;
• update the device.
The software can be downloaded from www.ekinex.com
website and its use is described in the application manual
of the ekinex EK-BG1-TP DALI Gateway. The software
requires Microsoft Windows (7 and later).
i
Note. In order to install and use the CGEKBG1TP
configuration software, it could be necessary the
installation of .NET Framework 4, which can bee
freely downloaded from Microsoft.com website.
Signaling LED
On the device front panel a signaling LED is present. If
there is no BUS power supply or there is a BUS error,
the signaling LED flashes quickly (2 pulses per second).
If there is BUS power supply but a BUS error occurs, the
signaling LED flashes slowly (1 pulse per second). If the
BUS signal is connected and working correctly, the LED
remains on steady.
Relationship with local commands: on power-up, in case
the bus connection is not present, the local command is
active. When the BUS connection is detected, the con-
trol passes to the BUS as long as the signal is present.
In the absence of the signal, if the local command is an
N.O.button, the control is passed to the local commands
when a N.O. button is pressed. On the other hand, if the
local command is 0-10V or 1-10V, the control immediately
passes to the local command.
Dimensions [mm]
4
71.00
62.0