DAE AMR130-v2.0 Посібник з монтажу
Переглянути онлайн або завантажити pdf Посібник з монтажу для Блок управління DAE AMR130-v2.0. DAE AMR130-v2.0 2 сторінки. Auto meter reading module
Auto Meter Reading Module
AMR130-v2.0
Installation Guide
1
Warnings & Precautions
Danger
To reduce the risk of electric shock, turn off all
sources of electrical power to the device during
installation or wiring.
Warnings
●
●
Follow these instructions accordingly, otherwise
damage may occur to the device.
●
Follow electrical rules and regulations in the
selection of wire materials and gauges.
●
Avoid having oil, water, metallic powder or other
foreign substances enter the device.
●
Avoid using the device in environments where it
will be exposed to steam, corrosive, or flammable
substances; which can cause short circuits, fires,
or explosions.
2
Front Panel & Terminals
System Indicator
Water Meter
Pulse Input
Input Power
DC 12-15V
Pulse
Input
Key
Pulse Indicator
Pulse Input
AMR130
RS485
USB
Micro USB
(Spare)
RS485
TX/RX Indicator
RS485 Port
AMR130-v2.0 installation guide-1.0e_P1
3
Dimensions
28
(1.1")
95
61
(3.74")
(2.4")
3
(0.12")
11 (0.43")
63 (2.48")
4
Mounting
Step 1
Pull latch down
Step 2
1
Display
Step 3
Push latch up
5
Wiring Diagram
26
(1.02")
Water Meter
30 (1.18")
35 (1.38")
30 (1.18")
Water Outlet
3 (0.12")
4 (0.16")
Unit : mm (inch)
Weight : 121.5g
*Tip:
After installation, the AMR display
should be synchronized through
software calibration (Modbus
protocol)
6
Wiring Detail
1. Please follow electrical regulations and recommendations
in selecting the wire size and type.
DIN rail
2. Ensure that the wires are making good contact with the
TS35/7.5 or 15
terminals and have been screwed securely.
3. Terminals can accept wires with size of no more than
2.0mm
2
.
2
1. Hook onto DIN rail
2. Push towards wall
UL2464 Shielded Twisted Stranded Copper Pair
Red+(R)
Red+(R)
*Warning:
Connect red to red, and black to white
Water Inlet
Input Power
-
+
DC 12-15V
7
Water Meter & RS485 Cable Detail
1. Use UL2464 shielded twisted stranded copper pair, 22-24
AWG recommended.
2. Terminate wire ends with cord end or blade lugs.
3. Ensure that the wires are screwed tightly to their
corresponding terminals.
4. Ensure that the positive and negative polarities are
correct.
Recommended:
Use cord end or blade lugs
Stranded
copper wire
Tip: Max cable length is 100 meters
Red+(R)
DC 12-15V
Pulse
Key
Input
Pulse Input
AMR130
RS485
USB
RS485
communication cable
Recommended:
Use cord end or blade lugs
UL2464 shielded twisted
stranded copper pair cable
IN
OUT