bolid S2000-SP2 Посібник користувача - Сторінка 5

Переглянути онлайн або завантажити pdf Посібник користувача для Пожежна сигналізація bolid S2000-SP2. bolid S2000-SP2 18 сторінок. Addressable two output alarm actuating unit

1.2

Specifications

Power inputs
Power input voltage
Consumed Current
Start-up time
PL/executive part insulation voltage
Number of outputs
Maximum commuting current per a single output
Maximum total commuting current for the unit
Circuit operability monitoring current, max
Circuit operability monitoring voltage
Commuting Voltage
Enclosure Protection Degree as per GOST 14254-2015
Resistance to mechanical exposure as per OST 25 1099-83
Vibration exposure:
Environmental category as per OST 25 1099-83
Operating temperatures
Weight
Overall dimensions
Non-stop operation
MTBF in the quiescent mode
Survival probability (after 1000 h)
Expected lifetime
As to immunity to man-made radio disturbance, the unit meets the requirements for Test Severity
Level III of the relevant standards listed in Appendix 'Б' of GOST R 53325-2012.
The unit passes the man-made radio disturbance standards prescribed for Class 'Б' equipment as
per GOST R 30805.22.
6
Parameter
- for executive elements
- for receive/transmit part
- for executive elements
- for receive/transmit part
- Frequency range
- Max acceleration
Value
2
10.2 through 28.4 V dc
via PL, 8 through 12 V
60 mA max(w/o regard to outputs'
current)
1 mA max
15 s
500 V
2
3 A
4 A
1.5 mA
5 V
10.2 through 28.4 V from the power
supply of the executive part
IP40
Arrangement Category III
1-35 Hz (for Category III)
0.5 g (for Category III)
O3
Minus 30 through + 55 °С
0.2 kg max
102×107×39 mm
24/7
80,000 hours min
0.98758
10 years
Table 1.2.1