6. Functional characteristics
DORMA ED 100 and ED 250 are electromechanical swing
door operators and suitable for various fields of application.
Select the respective version depending on the prevailing
door-leaf width and the door weight.
While the ED 100 is suitable for doors with a weight of up to
100 kg and a door width of 1,100 mm, the ED 250 is desi-
gned for doors with a width of 1,600 mm (1,400 mm when
installed at fire and smoke doors) and a door weight
of 250 kg.
Both operators may be installed as push-version with stan-
dard arm and as pull-version with slide channel.
All these variants are suitable for application at fire and
smoke doors.
The swing door operator opens the door automatically as
soon as an activator has been triggered.
In case a suitable locking device is installed, it will be unlo-
cked before the door starts to move.
The adjusted hold-open time starts as soon as the door is
open and the door closes automatically on expiry of the
adjusted time.
Users may access the door manually at any time. In this case
the operator has the function of a common door closer.
Switches
The mains switch is always installed on the side of the door
hinge, while the internal program switch is always installed
on the side of the main closing edge. The external program
switch is mounted within the close range of the door.
Mains switch
Power supply
1
OFF
2
AUTOMATIC
3
EXIT ONLY
PERMANENT
4
OPEN
5
without Function
MALFUNCTION
6
DORMA
Program switch
internal Program switch
1
2
1
3
4
2
4
3
5
external Program switch
Program switch
The program switch may be installed internally or externally
and is available in a 4-position and a 3-position version.
The 3-position program switch does not offer an EXIT ONLY
function.
Functions
OFF
The door opens automatically when the
Night-/Bank activator is triggered and closes
on expiry of the Night-/Bank hold-open time.
AUTOMATIC
The door opens automatically when one of
the activators is triggered and closes on
expiry of the adjusted hold-open time.
PERMANENT The door opens automatically and
OPEN
remains open until the function is deactiva-
ted.
EXIT ONLY
The door only opens automatically after the
internal activator or the Night-/Bank activator
has been activated. The door closes on expiry
of the adjusted hold-open time.
Selection of functions
Activate the desired function by pushing the respective key
on the external program switch (see picture at the bottom of
the left column).
When performing adjustments with the aid of the internal
program switch, you have to adjust both switches in a certain
combination:
The front switch is only adjusted to " I " if you want to adjust
the EXIT ONLY function.
OFF
Adjust both switches to "0".
AUTOMATIC
Adjust the front switch to "0",
and the other switch to "I".
PERMANENT OPEN
Adjust the front switch to "0",
and the other switch to "II".
EXIT ONLY
Adjust the front switch to "I",
and the other switch to "I".