Overview

The H1000 control panel is designed to interface with the elevator electronics using the "Form C"
relay output contacts of the H1000 panel. These relay output contacts make or break the
connection to individual elevator floor buttons. The connection to these buttons is provided by
the elevator company.
The Wiegand Reader (located in the elevator cab) requires 6 conductors which will be connected
to the elevator travel cable used by the elevator. The elevator travel cable terminates in the elevator
control room, and from this location the 6 reader wires will be used to connect to the reader port
of the H1000 panel.
Travel Cable
6 conductors
Wiegand Reader
The H1000 "Form C" relay output contacts are designed to switch only low voltage. An Elevator
Relay Interface Box is required to make the actual connection to the floor buttons in the elevator
electronics. The Elevator Relay Interface Box must be supplied by the elevator contractor. 12 volt
relays are to be used in the interface box. The H1000 output relay contacts will switch the 12 volt
coil of the relay in the interface box.
Under no circumstance is 110/120 or higher voltage to be present in the access control panel
(many elevators use 110Volts AC or DC in the floor button circuitry which is considered a lethal
voltage). A service bypass switch must be installed in the Elevator Relay Interface Box to allow for
fire alarm release of all the floors in the event of a fire alarm and to allow service of either the
access control system or the physical elevator. If a bypass switch is not installed, both technical
parties need to be present during service of either the access control system or the elevator, and
that can be quite costly.

Requirements

 Wiegand reader mounted inside the elevator cab.
 Elevator Relay Interface Box, supplied by elevator contractor.
 H1000 controller mounted in the elevator control room.
 Refer to reader manufacturer for reader wire specifications.
 H1000 relays should be used to switch low DC voltage, e.g. 12VDC.
 H1000 V1.1 controller and daughter card EX100 V1.1.
6 conductors
Elevator Cab
H1000 Elevator Control
Installation Guide
H1000 Panel
Page 4 of 20