NOTE n.1
NET
3PH-3W-2CT
3PH-4W
2PH-2W
1PH-2W
CT
Primary / Secondary of the current transformer (CT)
VT
Primary / Secondary of the voltage transformer (VT)
NOTE n.2
P AVG
Integration time of the average value (AVG) and peak value (MD) for
power (from 1 to 60 minutes)
I AVG
Integration time of the average value (AVG) and peak value (MD) for
current (from 1 to 60 minutes)
NOTE n.3
DIM
Enable / Disable dimming of the display
TIME
Time in seconds after which the display luminosity is reduced. (With DIM
enabled)
LIGHT
Luminosity level of the display
PULSE
Enable / Disable the fl ashing of the sine wave symbol
Electrex logo.
NOTE n.4
DEF
Selects the default network interface to be used for the communication
ETH
Enable / Disable the Ethernet (LAN) port
WIFI
Enable / Disable the WIFI port
NOTE n.5
DHCP
Enable / Disable the search for a DHCP server in the network
IP
IP address of the network interface
NETM
Subnet mask: defi nes the belonging range of a host within an IP
subnetwork
GWAY
IP address of the gateway
MESSAGE "CFG ERROR"
During the set up operation a "CFG ERROR" message could appear. This means that
some wrong parameters are inserted.
2 phases 3 wires, triangle
3 phases 4 wires, Star
2 phases 2 wires, biphase
1 phase 2 wires, monophase
light near the
CFG ERROR
DIP-SWITCH CONFIGURATION
DIP FUNCTION
1 Line termination resistance (120 Ohm)
2 Fail safe resistance B (-)
3 Fail safe resistance A (+)
4 Not used
* with RS-485 Master PUK activated
LAN 10/100 ETHERNET PORT
EXPBUS
The instrument is equipped with a Ethernet Lan 10/100 Auto-MDI/MDIX port.
For the connection can be used a data cable straight or crossover.
Note: the port is not a PoE (Power over Ethernet = device power supply via the Lan port)
type. The connection of the device to a PoE port is anyway accepted. The power supply
anyway must be always provided by an external power supplier.
The ExpBus port, confi gurable via Ethernet port on web pages:
- uses a multicast communication rated at 250kb/sec with collision management
- max cable length : 10 meters
- manages up to 16 modules (but technically can manage up to 126)
- uses the UTP cable, 4 wires used:
2 for the power supply at 9 Vdc
2 for the bidirectional communication
The modules will also power supply the ExpBus port
The cable must be connected in in-out modality (multidrop) as per the RS485 Bus.
SLAVE
OFF
OFF
OFF
OFF
ON
1
2 3 4
ETHERNET
EXPBUS PORT
MASTER *
ON
ON
ON
OFF
ON
1
2 3 4