Baumer CleverLevel LBFI Інструкція з експлуатації Посібник з експлуатації - Сторінка 3
Переглянути онлайн або завантажити pdf Інструкція з експлуатації Посібник з експлуатації для Вимірювальні прилади Baumer CleverLevel LBFI. Baumer CleverLevel LBFI 48 сторінок. Point level detection – hygienic/industrial level measurement
Table of contents
1.
Safety .......................................................... 3
2.
Construction and function ........................... 3
3.
Symbols in warning signs ............................ 4
4.
Transport and storage ................................. 4
5.
Assembly ..................................................... 4
6.
Electrical connection ................................... 7
7.
areas ........................................................... 8
1.
Safety
Intended use
The sensor must be used solely for the level
detection of liquids and solids with a dielectric
constant of at least 1.5.
The sensor must only be used for media against
which the housing material and sensor tip are
resistant.
Staff qualification
Only use staff who are trained for the activities
described. This applies in particular to assembly,
installation, configuration and troubleshooting.
Make sure that the staff have read and understood
these instructions.
2.
Construction and function
1
Fig. 1. Construction
f
L
µC
Fig. 2. Function
www.baumer.com
2
3
4
C
Operating Instructions
CleverLevel
Point level detection - hygienic/industrial
8.
Configuration ............................................. 10
9.
Troubleshooting ..........................................12
10.
Cleaning, maintenance and repair..............12
11.
Disposal .....................................................12
12.
Accessories ................................................12
13.
Technical data ............................................12
14.
Configuration overview ...............................13
Technical condition
Only use sensor in perfect technical condition.
Only use Baumer accessories.
Baumer will accept no liability for other
manufacturers' accessories.
Risk of burns from hot media
During operation the sensor housing may warm
up to over 50 ºC. When working with hot media
provide protection against burns.
1
Sensor tip
2
LED
3
Connection with M12 plug
4
qTeach detector
An electrode integrated into the sensor tip forms
a capacitor with the environment. The medium
determines the capacity value depending on
its dielectric constant (DC values). A resonant
circuit occurs together with a coil in the sensor
electronics. Depending on the resonance
frequency measured and the programmable trigger
threshold, the switch signal is activated.
LBFH/I
®
3 / 48