3 System Overview

3.1

General

The cable transducer is a linear measuring system with a CANopen interface. It supports scaling and presetting.
In consideration of "CAN in Automation" (CiA) Profile 406 for Encoders, it's an absolute linear encoder - Class C2
(exception diagnostic part).
3.2

Supported Profiles

Following CANopen profiles are supported:
CiA 301 / Version 4.1 (Communication)
CiA 305 / Version 1.0 (LSS)
CiA 406 / Version 3.2 (Encoder Profile)
o
Absolute encoder redundant with cable-pull: Absolute linear encoder
3.3

Supported CANopen Services

Following CANopen services are supported:
1 Network Management (according to CiA 301)
1 SDO Server (according to CiA 301)
2 TPDOs (according to CiA 301/CiA 406)
1 Emergency Producer (according to CiA 301/CiA 406)
1 Heartbeat Producer (according to CiA 301)
3.4

Function Principle

Overview

3.4.1
Figure 1: Function principle overview
Physical
[Inc]
Position

Scaling

3.4.2
The step size for all position objects can be adapted in the object 0x6005. The basic unit is nanometer
Example 1: A position step setting of 1'000'000 nm/step means that the position output unit is 1 mm.
Baumer_GCA5_CANopen_MA_EN_V1_02.docx
28.09.2016
User Zero
[Inc]
Point
Scaling
(Offset)
[Steps]
Direction
Correction