Amphenol Telect nrgCONTROL-BT Посібник з монтажу - Сторінка 7
Переглянути онлайн або завантажити pdf Посібник з монтажу для Контролер Amphenol Telect nrgCONTROL-BT. Amphenol Telect nrgCONTROL-BT 11 сторінок.
2.3 Grounding
1. Use a listed (approved) crimping tool to attach a listed (approved), dual-hole compression lug for
ground bolts onto ground wire. The grounding location is on the rear of the panel.
2. Lightly coat antioxidant on lug, ground terminal and surrounding contacting surface.
3. Insert the wire through the opening in the tie bar and connect the lug using the bolts and washers provided.
4. Tighten to 50 in/lb. (5.5 N•m), max.
5. Make sure input power is off (open breaker, phony fuse, open fuse holder at primary distribution panel, or PDU),
before connecting this panel's power input cables to that PDU.
WARNING! Before connecting input power cables, make sure the input power to the panel is turned off.
2.4 Input Wiring
1. For input wiring — wiring used as input power to this nrgCONTROL-BT panel — follow these steps:
Refer to Fig. 3
a. Remove the power connector from the rear of the panel.
3
b. Strip
/
-inch of insulation away from the wire used to power the controller.
8
c. Insert the wire into the connector and tighten the screw to hold the wire in place.
d. Repeat for each wire for the connector, paying attention to the positive and negative for each feed
(A and B).
2.5 nrgCONTROL nrgNET Connectivity
nrgNET is the Amphenol Telect proprietary communication link between nrgSMART panels and the nrgCONTROL
controller. The connection uses a single cable with four conductors to provide power and data communication.
nrgCONTROL-BT
Fig. 6: nrgNET shown without tie bar and service links
7
nrgNET1 and nrgNET2 leg
outputs to nrgSMART panels
nrgNET1 and nrgNET2 leg power fuses
Standard GMT style (4A)
All rights reserved. 07.20.2018 145122-4
1
5
/
-20 on
/
" centers
4
8
Amphenol Telect
1-509-926-6000 — telect.com