Переглянути онлайн або завантажити pdf Інструкція з монтажу для Блок управління Advanced Axis AX-CTY. Advanced Axis AX-CTY 2 сторінки. Local energy master box trip module
These instructions cover the installation, replacement and configuration of the AX-CTY module.
The AX-CTY is a module providing connection of Advanced Axis
module connects to any dedicated notification appliance circuit of an Axis
module or SLC loop NAC module).
Caution: Before installing or removing any module, remove all sources of power (AC and Battery).
Installing & Replacing the AX-CTY Module:
Installation:
Remove the AX-CTY module from its shipping package. Place in a standard electrical back box and wire to a
dedicated NAC circuit and Local Energy Masterbox.
Note: The AX-CTY module can be placed inside a standard electrical box with or without the AX-NACM (SLC
loop module).
Replacement:
Replacement is as simple as disconnecting the flying-leads of the AX-CTY module, that connect it to the dedicated
NAC circuit and Local Energy Masterbox, and reconnecting the removed field wiring to the new AX-CTY module.
AX-CTY Module Wiring:
The Red and Black flying- leads get wired to a dedicated notification appliance circuit (NAC), + and - respectively.
The two White flying-leads get wired to the Local Energy Masterbox trip coil (orange wires).
The NAC circuit must be programmed to activate on general alarm and be non-silenceable.
POWER LIMITED – Connect to power limited circuits only.
Wire range – 18-12 AWG
AX-CTY Module Specification
Operating Voltage
Operating Current
Quiescent
Alarm
Operating Temperature
Environment
Humidity
Dimensions
Weight
As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice
Doc Number:
682-150 AFS
Revision:
1
2
18 – 28 VDC
0 mA
1
0.5 A (max.) for
/
second
2
32-120°F (0-48°C)
Indoor, Dry
10-95% (non-condensing)
1
1
/
"H x 1"W x 8
/
"L (includes wire length)
2
2
0.8 oz
AX
panels to a Local Energy Masterbox. The AX-CTY
AX
panel installation (AX-LPD/AX-NAC
100 South Street, Hopkinton, Massachusetts 01748