Temperature (model ACD-31P & ACD-41PQ only)
RANGE
-50
C ~ 300
C
o
o
-58
F ~ 572
F
o
o
Type-K thermocouple range & accuracy not included
Add 3
C (or 6
F) to specified accuracy @ -20
o
o
Frequency
RANGE
5.00Hz ~ 500.0Hz
Sensitivity (Sine RMS)
40A range: > 4A
400A range: > 40A
1000A range: > 400A
600V range: > 30V
THD%-F
(model ACD-41PQ only)
1)
RANGE
0.0% ~999.9%
2)
THD-F is defined as:
1)
(Total Harmonic RMS / Fundamental RMS) x 100%
Range for Dual Display mode: 0% ~ 99%
2)
Specified accuracy @ ACA fundamental > 5A ; ACV fundamental > 50V
3)
Total Power Factor (PF)
RANGE
0.10 ~ 0.99
Specified accuracy @ ACA fundamental > 2A ; ACV fundamental > 50V
1)
C ~ -50
o
Harmonic order
Fundamental
2nd ~ 3rd
4th ~ 16th
17th ~ 46th
47th ~ 51st
F ~ 21st
3d
Accuracy
2.0% + 3
o
2.0% + 6
o
C (or @ -4
F ~ -58
o
o
Accuracy
0.5%+4d
Accuracy
1.5% of Reading + 6d
5.0% of Reading + 6d
2.5% of Reading + 6d
3.0% of Reading + 6d
4.5% of Reading + 6d
Accuracy
1)
22nd ~ 51st
17
C
F
F)
o
3)
5d