5 Piping installation
Pipe outer diameter
Insulation inner
(Ø
)
diameter (Ø
p
9.5 mm (3/8")
12~15 mm
12.7 mm (1/2")
14~16 mm
Ø
Ø
i
i
Ø
Ø
p
p
t
If the temperature is higher than 30°C and the humidity is higher
than RH 80%, the thickness of the insulation materials should be at
least 20 mm to prevent condensation on the surface of the
insulation.
Use separate thermal insulation pipes for the gas and liquid
refrigerant piping.
5.1.3
Refrigerant piping length and height
difference
The shorter the refrigerant piping, the better the performance of the
system.
The piping length and height differences must comply with the
following requirements.
Shortest allowable length per room is 3 m.
Refrigerant piping length to each indoor unit
Refrigerant piping total length
Height difference
outdoor-indoor
Outdoor unit installed
≤15 m
higher than indoor
unit
Outdoor unit installed
≤7.5 m
lower than at least 1
indoor unit
5.2
Connecting the refrigerant piping
DANGER: RISK OF BURNING/SCALDING
CAUTION
▪ No brazing or welding on site for units with R32
refrigerant charge during shipment.
▪ During installation of the refrigeration system, joining of
parts with at least one part charged shall be performed
taking into account the following requirements: inside
occupied spaces non-permanent joints are NOT
allowed for R32 refrigerant except for site made joints
directly connecting the indoor unit to piping. Site made
joints directly connecting piping to indoor units shall be
of non-permanent type.
CAUTION
Do NOT connect the embedded branch piping and the
outdoor unit when only carrying out piping work without
connecting the indoor unit in order to add another indoor
unit later.
Installation manual
10
Insulation thickness
)
(t)
i
≥13 mm
≥13 mm
≤20 m
≤30 m
Height difference
indoor-indoor
≤7.5 m
≤15 m
5.2.1
Connections between outdoor and indoor
unit using reducers
Total indoor unit capacity class that can be connected to this
outdoor unit:
Outdoor unit
2MXM40
2MXM50
Port
Class
2MXM40
A
15, 20, 25, 35
B
15, 20, 25, 35
2MXM50
A
15, 20, 25, 35, 42
B
15, 20, 25, 35
42, 50
(a)
Use optional accessory.
Reducer type
1
2
Connection example:
▪ Connecting a Ø9.5 mm pipe to a Ø12.7 mm gas pipe connection
port
a
b
a
Outdoor unit connection port
b
Reducer type 1
c
Reducer type 2
d
Flare nut for Ø12.7 mm
e
Inter-unit piping
Coat the threaded connection port of the outdoor unit where the flare
nut comes in with refrigeration oil.
Flare nut for (mm)
Ø12.7
NOTICE
Use an appropriate wrench to avoid damaging the
connection thread by overtightening the flare nut. Be
careful NOT to overtighten the nut, or the smaller pipe may
be damaged (about 2/3-1× the normal torque).
5.2.2
To connect the refrigerant piping to the
outdoor unit
▪ Piping length. Keep field piping as short as possible.
▪ Piping protection. Protect the field piping against physical
damage.
Total indoor unit capacity
class
≤6.0 kW
≤8.5 kW
Reducer
—
—
(a)
—
1+2
—
Connection
Ø12.7 mm → Ø9.5 mm
Ø12.7 mm → Ø9.5 mm
c
d
e
Tightening torque (N•m)
50~60
2MXM40+50A
R32 Split series