Daikin 4MXS80E3V3B2 Посібник з монтажу - Сторінка 8

Переглянути онлайн або завантажити pdf Посібник з монтажу для Кондиціонер Daikin 4MXS80E3V3B2. Daikin 4MXS80E3V3B2 16 сторінок.

Daikin 4MXS80E3V3B2 Посібник з монтажу

Refrigerant piping

1
Align the centres of both flares and tighten the flare nuts 3 or 4
turns by hand. Then tighten them fully with torque wrenches.
Use torque wrenches when tightening the flare nuts to prevent
damage to the flare nuts and to prevent escaping of gas.
1
Torque wrench
2
Spanner
3
Piping union
4
Flare nut
Flare nut
Ø6.4
Ø9.5
Ø12.7
Ø15.9
Valve cap tightening torque
Liquid pipe
26.5~32.3 N•m
Service port cap tightening torque
2
When connecting the flare nut, coat the flare inner surface with
ether oil or ester oil and initially tighten 3 or 4 turns by hand
before tightening firmly.
Installation manual
5
1
4
Flare nut tightening torque
14~17 N•m
33~39 N•m
50~60 N•m
63~75 N•m
Gas pipe
48.1~59.7 N•m
10.8~14.7 N•m

Purging air and checking gas leakage

When piping work is completed, it is necessary to purge the air and
check for gas leakage.
WARNING
Do not mix any substance other than the specified
refrigerant (R410A) into the refrigeration cycle.
2
When refrigerant gas leaks occur, ventilate the room
as soon and as much as possible.
3
R410A, as well as other refrigerants, should always
be recovered and never be released directly into the
environment.
Use a vacuum pump for R410A exclusively. Using the
same vacuum pump for different refrigerants may
damage the vacuum pump or the unit.
If using additional refrigerant, perform air purging from the
refrigerant pipes and indoor unit using a vacuum pump, then
charge additional refrigerant.
Use a hexagonal wrench (4 mm) to operate the stop valve rod.
All refrigerant pipe joints should be tightened with a torque
wrench at the specified tightening torque.
1
Connect the projection side (on which the worm pin is pressed)
of the charging hose coming from the gauge manifold to the gas
stop valve's service port.
2
Fully open the gauge manifold's low-pressure valve (Lo) and
completely close its high-pressure valve (Hi).
The high-pressure valve subsequently requires no operation.
3
Apply vacuum pumping. Check that the compound pressure
gauge reads –0.1 MPa (–760 mm Hg).
Evacuation for at least 1 hour is recommended.
4
Close the gauge manifold's low-pressure valve (Lo) and stop the
vacuum pump.
Leave as is for 4-5 minutes and make sure the coupling meter
needle does not go back.
If it does go back, this may indicate presence of moisture or
leaking from connecting parts. Repeat steps 2 – 4 after checking
all connecting parts and slightly loosening and retightening the
nuts.
5
Remove covers from liquid stop valve and gas stop valve.
6
Turn the liquid stop valve's rod 90 degrees counterclockwise
with a hexagonal wrench to open the valve.
Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from indoor unit's flare
and outdoor unit's flare and valve rods.
After the check is complete, wipe all soapy water off.
7
Disconnect charging hose from gas stop valve's service port,
then fully open liquid and gas stop valves.
Do not attempt to turn valve rod beyond its stop.
8
Tighten valve lids and service port caps for the liquid and gas
stop valves with a torque wrench at the specified torques. See
"Refrigerant piping work" on page 4
for details.