Daikin Air Conditioner Посібник з монтажу

Переглянути онлайн або завантажити pdf Посібник з монтажу для Кондиціонер Daikin Air Conditioner. Daikin Air Conditioner 1 сторінка. Daikin air conditioner
Також для Daikin Air Conditioner: Посібник з монтажу (9 сторінок), Посібник з монтажу (8 сторінок), Посібник з монтажу (17 сторінок), Посібник з монтажу (9 сторінок), Посібник з монтажу (9 сторінок), Посібник з монтажу (4 сторінок), Посібник з монтажу (9 сторінок)

Daikin Air Conditioner Посібник з монтажу
DAIKIN AIR CONDITIONER
Safety Precautions
• Read these Safety Precautions carefully to ensure correct installation.
• This manual classifies the precautions into WARNINGS and CAUTIONS. Be sure to follow all the precautions below: they are all important for ensuring safety.
WARNINGS
Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury.
CAUTIONS
Failure to follow any of CAUTION may in some cases result in grave consequences.
• The following safety symbols are used throughout this manual:
Be sure to establish a proper
Be sure to observe this instruction.
Never attempt.
earth grounding connection.
• After completing installation, test the unit to check for installation errors. Give the user adequate instructions concerning the use and cleaning of the unit according to the Operation Manual.
WARNINGS
• Installation should be left to the authorized dealer or another trained professional.
Improper installation may cause water leakage, electrical shock, fire, or equipment damage.
• Install the air conditioner according to the instructions given in this manual.
Incomplete installation may cause water leakage, electrical shock, fire or equipment damage.
• Be sure to use the supplied or exact specified installation parts.
Use of other parts may cause the unit to come to lose, water leakage, electrical shock, fire or equipment damage.
• Install the air conditioner on a solid base that is level and can support the unit's weight.
An inadequate base or incomplete installation may cause injury or equipment damage in the event the unit falls off the base or comes loose.
• Electrical work should be carried out in accordance with the installation manual and the national, state and local electrical wiring codes.
Insufficient capacity or incomplete electrical work may cause electrical shock, fire or equipment damage.
• Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance. Follow all appropriate electrical codes.
• For wiring, use a wire or cable long enough to cover the entire distance with no splices if possible. Do not use an extension cord. Do not put other
loads on the power supply.Use a only a separate dedicated power circuit.
(Failure to do so may cause abnormal heat, electric shock,fire or equipment damage.)
• Use the specified types of wires for electrical connections between the indoor and outdoor units. Follow all state and local electrical codes.
Firmly clamp the interconnecting wires so their terminals receive no external stresses. Incomplete connections or clamping may cause terminal overheating, fire or euipment damage.
• After connecting all wiring be sure to shape the cables so that they do not put undue stress on the electrical covers, panels or terminals.
Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock,fire or equipment damage.
• When installing or relocating the system, be sure to keep the refrigerant circuit free from all substances other than the specified refrigerant (R410A), such as air.
(Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise which may result in rupture, resulting in injury.)
• If any refrigerant has leaked out during the installation work, ventilate the room.
(The refrigerant produces a toxic gas if exposed to flames.)
• After all installation is complete, check to make sure that no refrigerant is leaking.
(The refrigerant produces a toxic gas if exposed to flames.)
• During pump-down, stop the compressor before removing the refrigerant piping.
If the compressor is still running and the shut-off valve is open during
pump-down, air will be sucked in when the refrigerant piping is removed, causing abnormally high pressure which could lead to equipment damage or and personal injury.
• During installation, attach the refrigerant piping securely before running the compressor.
If the compressor is not attached and the shut-off valve is open during pump-down, air will be sucked in when the compressor is run, causing
abnormally high pressure whichcould lead to equipment damage and personal injury.
• Install an leak circuit breaker, as required.
If an leak circuit breaker is not installed, electric shock may result.
• Be sure to establish a ground. Do not ground the unit to a utility pipe, arrester, or telephone ground.
Incomplete or inadequate grounding may cause equipment damage, or electrical shock and personal injury. A high surge current from lightning or other sources may cause damage to the air conditioner.
• Be sure to install a ground fault circuit interrupter breaker.
Failure to install a ground fault circuit interrupter breaker may result in electrically shocks or personal injury.
CAUTIONS
• Do not install the air conditioner where gas leakage would be exposed to open flames.
If the gas leaks and builds up around the unit, it may catch fire.
• Establish drain piping according to the instructions of this manual.
Inadequate piping may cause water damage.
• Note for installing the outdoor unit. (For heat pump model only.)
In regions of the country where the outside temperature is at or
below the freezing point, the drain may freeze. If so, it is recommended that an electric heater be installed in order to protect the drain from freezing.
• Tighten the flare nut according to the specified torque. A torque wrench should be used.
If the flare nut is tightened too much, the flare nut may crack over time and cause refrigerant leakage.
• Do not touch the heat exchanger fins.
Improper handling may result in injury.
• Be very careful about product transportation.
Some products use PP bands for packaging. Do not use any PP bands for a means of transportation. It is dangerous.
Indoor Unit Installation Drawings
A Mounting plate
B M3/16" X 1"L
The mounting plate should
be installed on a wall which
can support the weight of
the indoor unit.
1 3/16 or more
from ceiling
Cut thermal insulation pipe to an
appropriate length and wrap it with
tape, making sure that no gap is left
Front panel
in the insulation pipe's cut line.
1 15/16 or more from walls
(on both sides)
Air filters
Caulk pipe hole
gap with putty.
Service lid
This service lid is an open/close type.
• Remove the screws on the
service lid.
• Slide the service lid leftward.
• Rotate the service lid upward.
C Air-purifying filter with photocatalytic deodorizing function
Install Air-purifying
Air filter
filter with
C
Air-purifying filter
with photocatalytic
photocatalytic
deodorizing
deodorizing function
function
on air filter
Accessories
A Mounting plate
1
E Remote controller holder
B Mounting plate fixing
F Fixing screws for remote controller
10
screws M3/16" X 1"L
holder M1/8" X 13/16"L
C Air-purifying filter with
2
G AAA dry-cell batteries
photocatalytic deodorizing function
H Indoor unit fixing screws
D Wireless remote controller
1
M3/16" X 1/2"L
Choosing a Site
• Before choosing the installation site, obtain user approval.
1.
Indoor unit
• The indoor unit should be sited in a place where:
1) the restrictions on installation specified in the indoor unit installation drawings are met,
2) both air intake and exhaust have clear paths met,
3) the unit is not in the path of direct sunlight,
4) the unit is away from the source of heat or steam,
5) there is no source of machine oil vapour (this may shorten indoor unit life),
6) cool air is circulated throughout the room,
7) the unit is away from electronic ignition type fluorescent lamps (inverter or rapid start type) as they may shorten the
remote control range,
8) the unit is at least 3.5ft away from any television or radio set (unit may cause interference with the picture or sound).
2.
Wireless Remote Controller
1) Turn on all the fluorescent lamps in the room, if any, and find the site where remote control signals are properly
received by the indoor unit (within 23ft).
Installation Tips
1. How to remove the front grille.
1) Hold the grille by the tabs on the two sides and lift it until it stops with a click.
2) Supporting the front grille with one hand, release the lock by sliding down the knob with the other hand.
3) To remove the front grille, pull it toward yourself with both hands.
2. How to attach the front grille.
1) Set the 3 keys of the front grille into the slots and push them in all the way.
2) Supporting the front grille with one hand, fit the lock by sliding up the knob with the other hand.
3) Close the front grille slowly in this state. (Push the grille at the 3 points, two at both sides and in
the middle.)
3. How to remove the front panel.
1) Open the front grille.
2) Remove the screws (2 pcs) on the front panel.
3) Pull the lower part of the front panel toward you, then remove the front panel completely.
(There are 2 hooks on the upper part.)
If it is difficult to remove, open the front grille and raise the top grid, using a
screwdriver, to unhook the hooks.
4. How to attach the front panel.
1) Attach the front panel to the front grille, and lock the upper hooks (2 points) securely.
2) Tighten the screws (2) on the front panel.
3) Close the front grille.
5. How to set the different addresses.
1) When two indoor units are installed in one room, the two
wireless remote controllers can be set for different addresses.
6. PCB in the indoor unit
1) Remove the front panel.
2) Remove the sensor parts cover (2-screws), then
remove the electric parts box (1-screw).
Wireless
3) Slide the metallic cover to remove it. (4-claws on the
remote
electric parts box.)
controller
4) Cut the jumper JA on PCB.
J4
Address
7. Wireless remote controller
EXIST
1
CUT
2
1) Cut the jumper J4.
Intelligent-Eye Sensor
1.
Adjusting the angle
I How to attach the indoor
1) Once installation of the indoor unit is complete,
unit.
adjust the angle of the Intelligent-eye sensor to
Hook the claws of the bottom
ensure the detection area properly covers the room.
A Mounting
frame to the mounting plate.
(Adjustable angle: 15˚ to right and left of centre)
plate
If the claws are difficult to
hook, remove the front grille.
Clip
I How to remove the indoor
unit.
Push up the marked area (at
the lower part of the front
Bottom frame
Front grille
grille) to release the claws.
Mark (rear side)
If it is difficult to release,
remove the front grille.
2) Gently push and slide the sensor to adjust the
angle. Aim so that the sensor is pointing to the
centre of the room, or to the part of the room that is
most frequently used.
Wrap the insulation
pipe with the finishing
Moving the sensor to the left
tape from bottom to top.
3) After adjusting the angle, gently wipe the sensor
with a clean cloth, being careful not to scratch the
sensor.
Caution
1) Do not hit or violently push the Intelligent-eye
sensor. This can lead to damage and
malfunction.
2) Do not place large objects near the sensor. Also
keep heating units or humidifiers outside the
sensor's detection area.
Before screwing the remote
controller holder to the wall,
make sure that control
signals are properly received
by indoor unit.
D Wireless
remote controller
E
F
Remote
(M1/8" X 13/16"L)
controller holder
3P141697-1C
M04B018A
1.
Installing the mounting plate
1
K Operation manual
1
• The mounting plate should be installed on a wall which can support
the weight of the indoor unit.
1) Temporarily secure the mounting plate to the wall, make sure that
2
L Installation manual
1
the panel is completely level, and mark the boring points on the wall.
2) Secure the mounting plate to the wall with screws.
2
Recommended mounting-plate retention spots and Dimensions
Leveling mounting plate
2
Recommended
a
Dangle a weighted thread and
(Bolt size: M3/8)
mounting-plate
align thread with vertical arrow.
retention spots
b
Place a leveler
(6 spots in all)
4 1/8
on raised tab.
2 3/8
2 9/16
Gas pipe end
10 9/16
1 15/16
Liquid pipe end
30 7/8
Through-the-wall
hole ø2 9/16
Drain hose position
* The removed pipe port cover can be
kept in the mounting plate pocket.
2.
Boring a wall hole and installing wall embedded pipe
• For walls containing metal frame or metal board, be sure to use a
wall embedded pipe and wall cover in the feed-through hole to
prevent possible heat, electrical shock, or fire.
• Be sure to caulk the gaps around the
pipes with caulking material to prevent
Fit the key
into the slot.
water leakage.
1) Bore a feed-through hole of 2 9/16in in
the wall so it has a down slope toward
Slide up the knob.
the outside.
Raise and
Upper hook
remove
2) Insert a wall pipe into the hole.
Hook
Upper grille
3) Insert a wall cover into wall pipe.
4) After completing refrigerant piping, wiring, and drain piping, caulk
Screwdriver
pipe hole gap with putty.
Screwdriver
Filter guide
3.
Installing indoor unit
3-1. Right-Side, Right-Back, or Right-Bottom Piping
Claws (4 points)
Metallic cover
1) Attach the drain hose to the
J4
underside of the refrigerant pipes
Electric
parts box
with adhesive vinyl tape.
2) Wrap the refrigerant pipes and
ADDRESS:
JA
drain hose together with
JA
EXIST
1
Remove pipe port cover
ADDRESS
JB
CUT
Sensor
insulation tape.
2
here for right-side piping
parts cover
JC
PCB
Remove pipe port cover here for right-bottom piping
Refrigerant piping work
1.
Flaring the pipe end
1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward
so that the chips do not enter the pipe.
3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.
Warning
1) Do not use mineral oil on flared part.
Intelligent-eye
sensor
2) Prevent mineral oil from getting into the system as this would reduce the unit life.
15˚ 15˚
3) Never use piping which has been used for previous installations. Only use parts which are provided with the unit.
4) Do never install a refrigerant drier to this unit.
5) The drying material may dissolve and damage the system.
6) Incomplete or improper flaring may cause refrigerant gas leakage.
2.
Refrigerant piping
1) Align the centres of both flares and tighten the flare nuts 3 or 4 turns
by hand. Then tighten them fully with the torque wrenches.
• Use torque wrenches when tightening the flare nuts to prevent
damage to the flare nuts and escaping gas.
2) To prevent gas leakage, apply refrigeration machine oil on both
Moving the sensor to the right
inner and outer surfaces of the flare.
Coat here with refrigeration machine oil
2-1. Cautions on Pipe Handling
1) Protect the open end of the pipe against dust and moisture.
2)
All pipe bends should be as gentle as possible. Use a pipe
bender for bending.
(Bending radius should be 1 3/16 to 1 9/16in or larger.)
2-2. Selection of Copper and Heat Insulation materials
• When using commercial copper pipes and fittings, observe the following:
1) Insulation material: Polyethylene foam
Heat transfer rate: 0.041 to 0.052 kW/mK (0.024-0.030 Btu/fth˚F)
Refrigerant gas pipe's surface temperature reaches 230˚F max.
Choose heat insulation materials that will withstand this temperature.
2) Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.
Gas side
Liquid side
09/12 class
O.D. 3/8
O.D. 1/4
Thickness 0.031
3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
Indoor Unit Installation
3) Pass the drain hose and refrigerant pipes
through the wall hole, then set the indoor unit
on the mounting plate hooks by using the
markings at the top of the indoor unit as a
guide.
4) Open the front grille, then open the service lid.
(Refer to Installation Tips.)
5) Pass the interconnecting wires
from the outdoor unit through the
When stripping
Use tape measure
the ends of
as shown.
feed-through wall hole and then
interconnecting wires
Position the end of
in advance, bind right
through the back of the indoor unit.
ends of wires with
tape measure at .
insulating tape.
Pull them through the front side.
Wire guide
(Bolt size: M3/8)
3 3/4
Bend the ends of tie wires upward in advance for easier work. (If
the interconnecting wire ends are to be stripped first, bundle wire
ends with adhesive tape.)
6) Press the indoor unit's bottom panel with both hands to set it on the
mounting plate hooks. Make sure the wires do not catch on the
edge of the indoor unit.
3-2. Left-Side, Left-Back, or Left Bottom Piping
1) Attach the drain hose to the
Unit outline
underside of the refrigerant
3 3/8
4 5/16
pipes with adhesive vinyl tape.
(unit: in)
Remove pipe port cover here for left-bottom piping
Left-bottom piping
• How to set drain plug
2) Be sure to connect the drain hose to
the drain port in place of a drain plug.
Removed
pipe port
cover
A
Mounting
plate
Insert a hexagon wrench (3/16")
3) Shape the refrigerant pipe along the pipe path marking on the
mounting plate.
4) Pass drain hose and refrigerant pipes through the wall hole, then
set the indoor unit on mounting plate hooks, using the
the top of indoor unit as a guide.
5) Pull in the interconnecting wires.
6) Connect the inter-unit piping.
Inside
Outside
Wall embedded pipe
Drain
A Mounting plate
(field supply)
hose
Caulking
Caulk this hole
with putty or
caulking material.
Interconnecting
Wrap insulating tape around the bent portion of refrigerant pipe.
wires
Note:
Bind with plastic tape.
Overlap at least half the width of the tape with each turn.
ø2 9/16in
1) Wrap the refrigerant pipes and drain
Wall hole cover
(field supply)
hose together with insulation tape as
Wall embedded
Drain hose
pipe
right figure, in case of setting the drain
(field supply)
hose through the back of the indoor unit.
2) If it is difficult to fix the claws of the
bottom frame on the catches of the
mounting plate. Secure indoor unit to the
Bottom frame
mounting plate with screws (M3/16" x 1/2"L).
3-3. Wall Embedded Piping
Insert drain hose to this
Follow the instructions given under
depth so it won't be
pulled out of drain pipe.
Left-Side, Left-Back, or Left Bottom Piping
1 15/16"
Right-back piping
or more
1) Insert the drain hose to this depth so it
Bind coolant pipe and
Right-bottom piping
wont be pulled out of the drain pipe.
drain hose together with
Outer wall
insulating tape.
1.
Trial Operation and Testing.
(Cut exactly at
1-1 Measure the supply voltage and make sure that it falls in the specified range.
right angles.)
Remove burrs
1-2 Trial operation should be carried out in either cooling or heating mode.
Flaring
Set exactly at the position shown below.
In cooling mode, select the lowest programmable temperature; in heating mode, select the highest
A
Flare tool for R-410A
Conventional flare tool
programmable temperature.
Clutch-type
Clutch-type (Rigid-type)
Wing-nut type (Imperial-type)
Die
A
0 ~ 0.020"
0.039 ~ 0.059"
0.059 ~ 0.079"
1) Trial operation may be disabled in either mode depending on the room temperature.
2) After trial operation is complete, set the temperature to a normal level (78˚F to 82˚F in cooling mode, 68˚F to
Check
The pipe end must
75˚F in heating mode).
Flare's inner
surface must
be evenly flared in
3) For protection, the unit disables restart operation for 3 minutes after it is turned off.
be flaw-free.
a perfect circle.
Make sure that the
1-3 Carry out the test operation in accordance with the Operation Manual to ensure that all functions and
flare nut is fitted.
parts, are working properly.
The air conditioner requires a small amount of power in its standby mode. If the system is not to be used for
some time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.
If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original
operation mode when the circuit breaker is opened again.
Trial operation from Remote Controller
1) Press ON/OFF button to turn on the system.
2) Simultaneously press center of TEMP button and MODE button.
3) Press MODE button twice.
("
" will appear on the display to indicate that Trial Operation mode is selected.)
Flare nut tightening torque
4) Trial run mode terminates in approx. 30 minutes and switches into normal mode. To quit a trial
Gas side
Liquid side
operation, press ON/OFF button.
3/8 inch
1/4 inch
2.
24.1~29.4ft • Ibf
10.4~12.7ft • Ibf
Test Items.
Torque wrench
Valve cap tightening torque
Gas side
Liquid side
Spanner
3/8 inch
1/4 inch
Indoor and outdoor units are installed properly on
15.9~20.2ft • Ibf
solid bases.
Piping union
Flare nut
No refrigerant gas leaks.
Refrigerant gas and liquid pipes and indoor drain
Wall
Be sure to
hose extension are thermally insulated.
place a cap.
Rain
If no flare cap is
available, cover
Drain line is properly installed.
the flare mouth
with tape to keep
System is properly ground to earth.
dirt or water out.
The specified wires are used for interconnecting
wire connections.
Indoor or outdoor unit's air intake or exhaust has
clear path of air.
Shut-off valves are opened.
Indoor unit properly receives remote control
Gas pipe thermal insulation
Liquid pipe thermal
commands.
insulation
09/12 class
Inter-unit wiring
I.D. 0.472-0.590
I.D. 0.315-0.393
Gas pipe
Liquid pipe
Thickness 0.393 Min.
Gas pipe
Liquid pipe
insulation
insulation
Finishing tape
Drain hose
4.
A Mounting plate
Wiring
1) Strip wire ends (9/16in).
2) Match wire colours with terminal numbers on
indoor and outdoor units' terminal blocks and
firmly screw wires to the corresponding
Terminal block
terminals.
Electrical component box
1
2
3
Shape wires so that the service
3) Connect the earth wires to
Hang indoor unit's
lid will fit securely.
hook here.
the corresponding terminals.
Wire retainer
4) Pull wires to make sure that
A
Mounting plate
they are securely latched up,
Use the specified wire type.
then retain wires with wire
Back
Interconnecting
wires
retainer.
5) Shape the wires so
that the service lid
Lock nut
fits securely, then
Outdoor unit
Conduit
close service lid.
mounting
1
2
3
L
L
plate
1
2
When wire length
exceeds 33ft,
use 0.079in wires.
Conduit
3
Safety
Earth
Indoor
2
Power
unit
1
breaker
leakage
supply
15A
circuit breaker
60Hz 208/230V
Earth
Remove pipe
port cover here
Warning
for left-side
piping
1) Do not use spliced wires, stand wires, extension cords, or starbust connections, as
they may cause overheating, electrical shock, or fire. Follow all Local, and State
Left-side
piping
electrical codes.
Left-back
2) Do not use locally purchased electrical parts inside the product. (Do not overload
piping
the circuit by adding drain pump or other electrical equipment to unit terminals.)
Doing so may cause electric shock or fire.
Do not apply lubricating
3) When carrying out wiring connection, take care not to pull at the conduit.
oil (refrigerant machine
oil) when inserting
Application of causes
5.
When connecting to an HA system
deterioration and drain
leakage of the plug
1) Remove the front grille. (2 screws)
2) Remove the electrical wiring box. (3 screws)
3) Remove the metal plate electrical wiring cover. (4 tabs)
4) Remove the resin plastic electrical wiring cover. (2 tabs)
5) Attach the connection cord to the S21 connector and pull the harness out
markings at
through the notched part in the figure.
6) Replace the electrical wiring cover as it was, and pull the harness around, as shown in the figure.
Tab
Tab
Notched part
Press
Press
Slide
HA cord
Tab
Tab
Press
HA connector (S21)
Slide
Press
3) Remove the metal
Screws
4) 5) Attach to the S21
plate electrical
wiring cover.
connector and take the
harness out of the notched
part on the mounting.
6) Pull-around figure
6.
Drain piping.
A
The drain hose
Mounting
1) Connect the drain
should be inclined
2) Remove the air
plate
downward.
filters and pour
hose, as described
Refrigerant
No trap is permitted.
pipes
some water into
below
Do not put the end
the drain pan
of the hose in water.
to check the water
flows smoothly.
H M3/16" x 1/2"L (2 points)
Extension drain hose
3) When drain hose requires extension, obtain an extension
Indoor unit
drain hose
hose commercially available. Be sure to thermally
Inner wall
insulate the indoor section of the extension hose.
Heat insulation tube (Field supply)
4) When connecting a rigid polyvinyl chloride pipe (nominal diameter 1/2in) directly to the drain
hose attached to the indoor unit as with embedded piping work, use any commercially
available drain socket (nominal
Drain hose
diameter 1/2in) as a joint.
Vinyl chloride
Commercially
Commercially
Drain hose supplied with
drain pipe
the indoor unit
available drain socket
available rigid polyvinyl
(VP-30)
(nominal diameter 1/2in)
chloride pipe
(nominal diameter 1/2in)
Trial Operation and Testing
Test Items
Symptom
Check
Fall, vibration, noise
Incomplete cooling/heating function
Water leakage
Water leakage
Electrical leakage
Inoperative or burn damage
Incomplete cooling/heating function
Inoperative