9. TEST RUN

] 1

9.1. Test run using PCB (Outdoor unit)

• Refer to the Installation Manual for the outdoor unit if the PCB for the outdoor unit is to
be used for the test run.
] 1

9.2. Test run using remote controller

• Refer to the Installation Manual for the remote controller to perform the test run using
the remote controller.
• When the air conditioner is being test run, the OPERATION and TIMER indicator lamps
fl ash slowly at the same time.

10. CHECK LIST

Pay special attention to the check items below when installing the indoor unit(s). After
] 1
installation is complete, be sure to check the following check items again.
Check items
Has the indoor unit been
Vibration, noise, indoor unit may drop
installed correctly?
Has there been a check for
No cooling, No heating
gas leaks (refrigerant pipes)?
Has heat insulation work
Water leakage
been completed?
Does water drain easily
Water leakage
from the indoor units?
Is the voltage of the power source
the same as that indicated on
No operation, heat or burn damage
the label on the indoor unit?
Are the wires and pipes all
No operation, heat or burn damage
connected completely?
Is the indoor unit earthed
Short circuit
(grounded)?
Is the connection cable the
No operation, heat or burn damage
specifi ed thickness?
Are the inlets and outlets
No cooling, No heating
free of any obstacles?
Does start and stop air
conditioner operation by remote
No operation
controller or external device?
After installation is completed, has
the proper operation and handling
been explained to the user?
If not performed correctly
Check box

11. ERROR CODES

If you use a wired type remote controller, error codes will appear on the remote controller
1
display. If you use a wireless remote controller, the lamp on the photodetector unit will
output error codes by way of blinking patterns. See the lamp blinking patterns and error
codes in the table below.
Error display
OPERATOR
TIMER
indicator lamp
indicator lamp
indicator
(green)
(orange)
lamp (red)
(1)
(2)
(1)
(4)
(1)
(6)
(3)
(1)
(3)
(2)
(4)
(1)
(4)
(2)
(5)
(1)
(5)
(3)
(9)
(15)
Display mode
: 0.5s ON / 0.5s OFF
: 0.1s ON / 0.1s OFF
( ) : Number of fl ashing
Wired Remote Controller Display
Wired Remote
FILTER
Controller Error
Error contents
CODE
Remote controller
communication
error
Anomalous network
communications
Parallel
communication
error
Power frequency
error
Model information
error/EEPROM
accession error
Room temperature
thermistor error
Indoor heat
exchanger
temperature
thermistor error
Indoor fan motor
error
Drainage error
Outdoor unit error
Error code
En-16