7.3. Function setting

• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air
tight test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
Setting number
number
00 Standard
Filter indica-
01 Longer
11
tor interval
02 Shorter
00 Enable
01 Disable
Filter indica-
13
Display only on
tor action
02
central remote
controller
(Forbidden)
20
(Forbidden)
23
00 Standard
Horizontal
01 Left half
swing airflow
24
direction
02 Right half
(Forbidden)
26
(Forbidden)
27
00 Standard
Cool air
01 Adjust (1)
temperature
30
trigger
02 Adjust (2)
00 Standard
01 Adjust (1)
Heat air
02 Adjust (2)
temperature
31
trigger
03 Adjust (3)
00 Enable
Auto restart
40
01 Disable
00 Super low
Follow the
Cool Air
43
setting on
Prevention
01
the remote
controller
00 Start/Stop
Emergency
01
stop
External
46
control
02 Forced stop
00 All
Error report
Display only on
47
target
01
central remote
controller
Follow the
Fan set-
setting on
ting when
00
the remote
cooling
49
controller
thermostat
OFF
01 Stop
Forced ther-
00
mostat off
01
02
03
Switching
04
function for
60
(Forbidden)
external
05
inputs
06
07
08
Refrigerant
09
leak detection
(Forbidden)
61
00
(Forbidden)
62
00
Single
setpoint auto
00
mode
Auto mode
68
type
(traditional)
Dual setpoint
01
auto mode
En-13
Default
Details
Adjust the filter cleaning interval noti-
fication. If the notification is too early,
change to setting 01. If the notifica-
tion is too late, change to setting 02.
Enable or disable the filter indicator.
Setting 02 is for use with a central
remote controller.
Adjust the horizontal swing airflow
direction.
(For horizontal swing equipped
models)
Adjust the cool air trigger tempera-
ture. To lower the trigger tem-
perature, use setting 01. To raise the
trigger temperature, use setting 02.
Adjust the heat air trigger tempera-
ture. To lower the trigger temperature
by 6 degrees C, use setting 01. To
lower the trigger temperature by 4
degrees C, use setting 02. To raise
the trigger temperature, use setting
03.
Enable or disable automatic system
restart after a power outage.
Restrain the cold airflow with making
the airflow lower when starting heat-
ing operation. To correspond to the
ventilation, set to 01.
Allow an external controller to start
or stop the system, or to perform an
emergency stop.
* If an emergency stop is performed
from an external controller, all re-
frigerant systems will be disabled.
* If forced stop is set, indoor unit
stops by the input to the external
input terminals, and Start/Stop by a
remote controller is restricted.
Change the target for reporting
errors. Errors can either be reported
in all locations, or only on the central
remote controller.
When set to 01, the fan stops when
the thermostat is OFF in cooling
operation. Connection of the wired
remote controller (2-wire type or
3-wire type) and switching its therm-
istor are necessary.
Setting is required when connecting
a refrigerant-leak detecting device.
(only for J-IIIL series)
Switch the setting method of
auto mode to single or dual
(cooling/heating).
For heat pump systems, it is
necessary to set the master indoor
unit (by wired remote controller).
Function
Function
Setting number
number
00 0°C
01 0.5°C
02 1.0°C
03 1.5°C
Deadband
04 2.0°C
69
value
05 2.5°C
06 3.0°C
07 3.5°C
08 4.0°C
09 4.5°C
(Forbidden)
70
00
(Forbidden)
72
00
(Forbidden)
73
00
(Forbidden)
74
00
(Forbidden)
75
00
7.3.1. Button name and function
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
7.3.2. Checking the function settings
Press and hold the "MANUAL AUTO" button on the indoor unit for 3 seconds to check
the function settings. It is necessary to disconnect the power in order to return to normal
operation mode.
(1) Indoor unit and refrigerant address indication
Indication pattern
Indicator name
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
• Indoor unit address example
(Example) ADDRESS : 24
OPERATION
ON
indicator
lamp (Green)
OFF
ON
TIMER
indicator
0.5s 0.5s 0.5s 0.5s
lamp (Orange)
OFF
ON
FILTER
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
indicator
OFF
lamp (Red)
• Indoor unit address example Refrigerant address example
(Example) ADDRESS : 30
OPERATION
ON
indicator
1.0s
lamp (Green)
OFF
TIMER
ON
indicator
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
lamp (Orange)
OFF
ON
FILTER
indicator
OFF
lamp (Red)
Default
Details
Choose the minimum temperature
between cooling and heating
settings (deadband) for Dual
setpoint auto mode (set in No. 68).
MANUAL AUTO button
Indication pattern
Indoor unit
Refrigerant address
address
ON
Flash (1.0s ON/1.0s OFF)
Address: tens place (0.5s ON/0.5s OFF)
Address: ones place (0.5s ON/0.5s OFF)
1 cycle 12 sec
ON
10 sec
8 sec
1 cycle 12 sec
1.0s
1.0s
1.0s
1.0s
1.0s
1.0s
9 sec
OFF