6.3.2 Checking the function settings
Press and hold the "MANUAL AUTO" button on the indoor unit for 3 seconds to check
the function settings. It is necessary to disconnect the power in order to return to normal
operation mode.
(1) Indoor unit and refrigerant address indication
Indication pattern
Indicator name
Indoor unit address
OPERATION indicator lamp (Green)
ON
TIMER indicator lamp (Orange)
Address: tens place (0.5s ON/0.5s OFF)
FILTER indicator lamp (Red)
Address: ones place (0.5s ON/0.5s OFF)
• Indoor unit address example
(Example) ADDRESS : 24
ON
OPERATION indicator
lamp (Green)
OFF
ON
TIMER indicator lamp
0.5s 0.5s 0.5s 0.5s
(Orange)
OFF
ON
FILTER indicator lamp
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
(Red)
OFF
• Refrigerant address example
(Example) ADDRESS : 30
ON
OPERATION indicator
1.0s
lamp (Green)
OFF
ON
TIMER indicator lamp
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
(Orange)
OFF
ON
FILTER indicator lamp
(Red)
OFF
• Setting details
Function number
01
Indoor unit address
02
Refrigeration address
For use with a remote controller, set all rotary switches to 0, and refer to "6.1. Setting the
address" for details.
All switches are set to 0 at the factory.
(2) Others
Indication pattern
Indicator Name
OPERATION indicator lamp (Green)
TIMER indicator lamp (Orange)
FILTER indicator lamp (Red)
(Example) Function : 31, Setting number : 2
OPERATION indicator
ON
0.5s
0.5s
0.5s
lamp (Green)
OFF
ON
TIMER indicator lamp
0.5s 0.5s
(Orange)
OFF
ON
FILTER indicator lamp
0.5s
0.5s
0.5s
(Red)
OFF
Indication pattern
Refrigerant address
Flash (1.0s ON/1.0s OFF)
1 cycle 12 sec
ON
10 sec
8 sec
1 cycle 12 sec
1.0s
1.0s
1.0s
1.0s
1.0s
1.0s
9 sec
OFF
Item
Setting number
00 to 63
00 to 99
Indication pattern
Function number; tens place (0.5s ON/0.5s OFF)
Function number; ones place (0.5s ON/0.5s OFF)
Setting number: (0 to 9) (0.5s ON/0.5s OFF)
1 cycle 12 sec
0.5s 0.5s 0.5s
9 sec
11 sec
10 sec
0.5s

6.4. External input and external output (Optional parts)

In this setting, you need to remove the front panel. Refer to "8. FRONT PANEL REMOVAL
AND INSTALLATION".
004/007/009 model
DIP switch
(SET 2)
ON
OFF
SW4
SW3
SW2
SW1
Apply voltage terminal
030/034 model
Controller PCB
DIP switch
(SET 2)
ON
OFF
SW4
SW3
SW2
SW1
Apply voltage terminal
6.4.1 External input
• Indoor unit can be Operation/Stop, Emergency stop or Forced stop by using indoor unit
PCB CNA01 or CNA02.
• "Operation/Stop" mode, "Emergency stop" mode or "Forced stop" mode can be selected
with function setting of indoor unit.
• Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04.
• A twisted pair cable (22 AWG) should be used. Maximum length of cable is 150 m.
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
Input select
Use either one of these types of terminal according to the application. (Both types of
terminals cannot be used simultaneously.)
● Apply voltage terminal ([CNA01], [CNA03])
When a power supply must be provided at the input device you want to connect, use the
Apply voltage terminal ([CNA01], [CNA03]).
DC power supply
12 to 24V
Load
resistance
*a
Load
resistance
*a
Load
resistance
*a
Connected unit
*1: Make the power supply DC 12 to 24 V. Select a power supply capacity with an ample
surplus for the connected load.
Do not impress a voltage exceeding 24 V across pins 1-2, and 1-3.
*a: The allowable current is DC 5 mA to 10 mA. (Recommended: DC 5 mA)
Provide a load resistance such that the current becomes DC 10 mA or less.
Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).
*b: The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.
Dry contact
terminal
(CNA02)
(CNA04)
Controller
PCB
Output
terminal
(CNB01)
(CNA01) (CNA03)
Output
terminal
(CNB01)
Dry contact
terminal
(CNA03)
(CNA01)
(CNA04)
(CNA02)
P.C.B
*1
CNA01
*b
CNA03
En-10