Draper Low Voltage, Remote Control, Serial and Network Wiring Guide
Wiring Diagram for LVC-III with Low Voltage Radio Frequency Remote Control
➀ Wire Screen according to diagram.
➁ Before you can send commands, the RF receiver must "learn" the remote
transmitter. When the RF receiver fi rst receives power, a red LED on the
bottom of the receiver activates. This means it is in learning mode. To
"learn" the transmitter, simply point it at the RF receiver and hold down the
"up" button until the red LED goes out.
➂ Once the remote is learned, press "Up" to test the screen. If screen goes
down, up and down wires from motor should be switched. Motor directions will
now be reversed.
➃ To learn a second transmitter (up to fi ve total allowed), press the "learn"
button on the bottom of the receiver, and repeat step 2 (you will have 10
seconds after pressing the "learn" button).
Wire to connect power to LVC-III should be between 18 AWG and 12 AWG (solid or stranded) 2 conductors with ground. Wire size needs to be suffi cient to
carry the motor load. Red and Black wires are the "open" and "close" leads from the motor. The LVC-III comes enclosed in a metal box conforming to the Na-
tional Electric Code (NEC). RF receiver is connected to LVC-III using low voltage modular data or telephone cord (RJ11), which is isolated from the AC power
line. This wire is commonly called Silver Satin. It must be electrically straight (see explanation on page 2). The RF receiver must be within 1,000 feet of the LVC-
III. A dry contact wall switch may also be connected to the MC1 using 3-conductor wire.
➀ Wire Screen according to diagram.
➁ Press "Up." If screen goes down, up and down wires
from motor should be switched. Motor directions will now be reversed.
Wire to connect power to LVC-III should be between 18 AWG and 12 AWG (solid or stranded) 2 conductors with ground. Wire size needs to be suffi cient
to carry the motor load. Red and Black wires are the "open" and "close" leads from the motor. The LVC-III comes enclosed in a metal box conforming to the
National Electric Code (NEC). IR Eye is connected to LVC-III using low voltage modular data or telephone cord (RJ11), which is isolated from the AC power line.
This wire is commonly called Silver Satin. It must be electrically straight (see explanation on page 2). The IR eye must be within 100 feet of the LVC-III. A dry
contact wall switch may also be connected to the LVC-III using 3-conductor wire.
LVC-III
Dashed wiring by electrician
Wiring Diagram for LVC-III with Low Voltage Infrared Remote Control
LVC-III
Transmitter range: 70 feet
www.draperinc.com
White-Neutral (Common) to screen & 110-120V AC
Red-to screen (directional)
Brown-to screen (directional)
Yellow-to 110-120V AC
Black-to 110-120V AC
Green-Ground
Eye Port
Electrically Straight
Data Cable
Aux Port
Transmitter range: 100 feet
White-Common to screen & 110-120V AC
Red-to screen (directional)
Brown-to screen (directional)
Yellow-to 110-120V AC
Black-to 110-120V AC
Green-Ground
Eye Port
Electrically Straight
Data Cable
Aux Port
IR Transmitter
(765) 987-7999
RF Receiver
RF Transmitter
Dashed wiring by electrician
IR Eye