B. For strand wiring
(1) Use ring terminals with insulating sleeves as shown in the figure below to connect to
the terminal block.
(2) Securely clamp the ring terminals to the cables using an appropriate tool so that the
cables do not come loose.
(3) Use the specified cables, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw-
driver that is too small, otherwise, the screw heads may be damaged and prevent the
screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table for the terminal screw tightening torques.
(7) Please do not fix 2 power supply cables with 1 screw.
Strip 10 mm
Screw with
special washer
Cable
Ring terminal
Terminal block
Use ring terminals and tighten the terminal screws to the specified torques, otherwise,
abnormal overheating may be produced and possibly cause heavy damage inside the
unit.
Terminal number
M4 screw (Power supply/L, N, GND)
5.3.2 Transmission and Remote controller cable
Transmission cable
20 mm
Shield
cable
(no film)
35 mm
• Connect remote controller and transmission cables as shown in figure below.
GOOD
Different diameter
Tighten the terminal screws to the specified torques, otherwise, abnormal overheating
may be occurred and possibly cause serious damage inside the unit.
M3 screw (Transmission /X1, X2)
(Remote controller /Y1, Y2)
To peel the sheath from the lead cable, use a dedicated tool that will not damage the
conductor cable.
When installing a screw on the terminal block, do not cut the wire by overtightening the
screw. On the other hand, an under tightened screw can cause faulty contact, which will
lead to a communication failure.
En-7
Ring terminal
Screw with
special washer
Ring terminal
Cable
WARNING
Tightening torque
1.2 to 1.8 N·m (12 to 18 kgf·cm)
Remote controller cable
20 mm
PROHIBITED
Connect to 1 side
WARNING
Tightening torque
0.5 to 0.6 N•m (5 to 6 kgf•cm)
CAUTION

5.4. Wiring

(1) Open the intake grille. Refer to "8. FRONT PANEL REMOVAL AND INSTALLATION".
(2) Remove the wire cover and remove the cable clamp.
004/007/009 model
Wire cover
Screw
Sleeve
(3) Connect the end of the connection cable fully into the terminal block.
004/007/009 model
Symbol Connection cable
A
L
B
N
C
D
E
X1
F
X2
G
Y1
H
Y2
EV kit cable connecting (EEV external model only)
EV kit cable
When you attach the cable clamp, make sure that the cables are not jutting out from the
clamp or being pinched by the clamp.
030/034 model
I
H
G
F
E
D
C
Cable tie
(acces-
sories)
030/034 model
Cable
Cable
clamp
clamp
Screw
Wire cover
H
Power supply cable
G
Earth (ground) for
F
power supply cable
E
Earth (ground) for
transmission cable,
wired remote control-
C
ler cable (if neces-
D
sary) and EV kit cable
(EEV external model
only)
Transmission cable
Wired remote control-
ler cable (nonpolar)
Cable clamp
(Clamp only the
power supply cable)
Earth (ground) wire of EV kit cable
Connect
After connecting the EV kit cable, slide the tube (included with
the EV kit) over the connector to protect it.
Tube
Connect
A
B
L
N
X1
X2
Y1
Y2
Y3
Cable
clamp
Screw
A
B
Y1 Y2
L
N
X1
X2
Cable tie (Small)
Symbol Connection cable
A
L
Power supply cable
B
N
C
Earth (ground) for
power supply cable
D
X1
Transmission cable
E
X2
F
Earth (ground) for
transmission cable
and wired remote
controller cable (if
necessary)
G
Y1
Wired remote control-
ler cable (nonpolar)
H
Y2
I
Y3
Do not use