Carlin EZ-Temp 90300 Технічний паспорт - Сторінка 3

Переглянути онлайн або завантажити pdf Технічний паспорт для Системи управління Carlin EZ-Temp 90300. Carlin EZ-Temp 90300 4 сторінки. Microprocessor temperature controls

Model 90300 Microprocessor Temperature Controls — Data sheet
Configurations
Mounting – 90300 controls mount to any standard well. Mount
the 90300 directly to a well (new or existing) with hardware
supplied in the separate well mounting kit. See below for
dimensions.
Well Kits – Wells for 90300 sensors are available in the sizes shown
below. Well kits include sensor mounting hardware designed to
hold sensor securely in position.
Sensors – Sensors are available separately for 90300 only.
Error Codes
Error Code
Primary (K2) relay is welded on. Note: If the control is reset
01
from error code 01, the red LED will flash every 5 seconds
indicating the control must be replaced.
Primary & Safety relays (K1 and K2) on. The control cannot
02
be reset from error code 02 and must be replaced.
03
Primary & Safety relays (K1 and K2) are off
05
Simulated High Temp lockout
Temp is above set high temp but below thermistor high
06
(250°F)
16
AC line frequency out of tolerance
07
10
1 1
12
13
,
,
,
,
,
Reason
Internal hardware safety failure – unit should be replaced. Contact customer service for additional informa-
14
15
,
tion. 1-800-989-2275
3"
Error Code
20
Temp sensor 1 out of range failure
21
Temp sensor 2 out of range failure
22
High limit temp sensor out of range failure
23
Temp sensor 1 pin is open
24
Temp sensor 2 pin is open
25
High limit temp sensor is open
4
3
/
"
4
4
3
/
"
8
Reason
MN90300B 072016