Trouble
Shooting
Unit Repairs
This equipment is warranted to be free from defects of material
and workmanship. It is sold subject to our mutual agreement that the
liability of Athena Controls, Inc. is to replace and/or repair at its
factory, provided the equipment is returned, transportation prepaid
within (2) years of its purchase.
The purchaser agrees that Athena Controls, Inc. shall assume no
liability for consequential damages resulting from its use or
packaging of shipments returned to the factory.
Components which wear or which are damaged by misuses are not
warranted. These include contact points, fuses and triacs. Units
which have been rewired by customer are not warranteed.
Specifications are subject to change without notice.
Athena Controls Inc., 5145 Campus Drive
Plymouth Meeting, PA 19462
Front dark - no instrument power, blown fuse or burned
out transformer.
Process display shows CCCC - Open thermocouple.
Short terminals 1 and 2, should indicate temperature at
back of case. Repair or replace thermocouple.
About Half Or Twice Expected Reading- Check
position of ºC or ºF switch. Short 1 and 2 to read room
temperature. 22-30 is %, 70-85 is ºF
About 30% Error - Wrong thermocouple type.
Disconnect couple. "J" units over range above 1400°F,
"K" above 2000°F + .
No Heat - Heater wiring, wrong output module, blown
fuses.
Heat Stays On- Welded relay contacts or shorted
output module. Check for cause and correct the
components.
Process Display Shows 0000 Or Initially Displays Room
Temperature Then Counts Down Scale As Process
Warms - Check for reversed thermocouple.
It is recommended that units requiring service be
returned to an authorized service center. When a
controller is returned for service, a note stating the
problem should accompany the unit. To eliminate
service delay, consult the factory prior to returning any
unit.
A spare parts list can be supplied upon request if
complete model number, serial number and
temperature range is supplied.
Warranty
(215) 828-2490