HARD WIRING – LINE VOLTAGE
CAUTION
If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified persons in
order to avoid a hazard.
The dehumidifier comes with a power cord that has a NEMA 6-15P
plug that can simply be plugged into a corresponding NEMA 6-15R
receptacle� The plug can be removed and replaced by hard-wired
electrical service if desired�
United States Installation: Make all electrical connections in accordance
with the current edition of the NEC ANSI/NFPA 70 and any local codes
or ordinances that may apply�
Canada Installation: Make all electrical connections in accordance with
the current edition of the Canadian Electrical Code CSA C22�1 and any
local codes or ordinances that may apply�
Voltage
Recommended Breaker Size
Recommended Wire Gauge
Maximum Fuse or Breaker Size (MOC)
Minimum Circuit Ampacity (MCA)
FIGURE 9 – HARD WIRING TO REPLACE THE POWER CORD
DISCONNECT
POWER CORD
WIRES
L2
L1
GND
WHT
BLK
GND
1. Disconnect electrical service at the main fuse or circuit breaker�
2. Run electrical service to where the dehumidifier is to be installed
3. Remove the side panel from the dehumidifier�
4. Loosen the terminal screws securing the power cord wires to the
5. Use channellock pliers to remove the strain relief and power cord
6. Route the service wires through the opening in the dehumidifier and
7. Insert the black service wire into the L1 terminal and the white
8. Insert the ground wire (bare or green) of the electrical service into
Model A210V1
208-240 VAC,
single phase, 60 Hz
9. Reattach the side panel to the dehumidifier�
15A
10. Restore electrical service at the fuse or circuit breaker�
14 AWG, Copper
19A
11A
following all required local and national codes and standards�
terminal blocks and ground lug�
from the unit� Pinch the side of the strain relief to release it from the
opening in the sheet metal and pull it away from the dehumidifier�
secure the cable or conduit to the opening in the dehumidifier using
fittings/clamps intended for the conduit/cable used�
service wire into the L2 terminal� Secure the wires into the terminals
by tightening the terminal screws�
the ground lug and secure it in place by tightening the ground lug
screw�
CONNECT THE BARE OR
GREEN GROUND WIRE
TO THE GROUND LUG
AS SHOWN
L2
GND
WHT
CONNECT THE
LINE (BLK) AND
NEUTRAL (WHT)
WIRES TO THE
POWER BLOCK
AS SHOWN
L1
BLK
GND
90-2401
English 7