ANDERSON-NEGELE MPP Посібник зі встановлення та запуску - Сторінка 2

Переглянути онлайн або завантажити pdf Посібник зі встановлення та запуску для Передавач ANDERSON-NEGELE MPP. ANDERSON-NEGELE MPP 4 сторінки. Modular pressure transmitter

USER INTERFACE GUIDE
The Anderson MPP Modular Pressure Transmitter is factory calibrated to the URL (upper range limit) and configured to the range
and units specified by the order matrix number. Range, pressure units, output damping and analog scale (HART only) may be easily
modified by the user. The Display Interface (DI) provides user feed back for menu functions, displays diagnostic error codes and
nominally loop current or process variable.
The Modular Pressure Transmitter configuration parameters are sorted into three modes, and are accessible via the button along the
bottom of the display interface. While the cover is removed, do not allow moisture to enter the housing.
0%
D
ò
own
E
xecute
Display Interface

SENSOR CONFIGURATION

Each instruction assumes starting from RUN mode which is default at power on and process value is displayed.
CALIBRATION – Zero
NOTE – For ABSOLUTE stems zero calibration is disabled as zeroing is not possible in atmospheric conditions.
Zeroing the sensor provides the best accuracy when clamped into the application therefore negates possible positioning and clamping
errors. Be sure sensor is exposed to zero psig when performing this function.
1.
Press both "D" and "M" simultaneously for approximately 5 seconds – Sensor displays 4.00 milliamp (HART version), or
0.00 (FFB version) for gauge, for compound sensor displays appropriate output for set range
Native Units: PSI or Bar
1.
Press "M" – Sensor displays "COnF"
2.
Press "E" – Sensor displays "PSI" or "BAR"
3.
Press "U" or "D" – Sensor toggles between "PSI" or "BAR"
4.
Press "M" to proceed to the next operation
Note: When changing units configuring range is now required
50%
100%
PHARMACEUTICAL
SERIES
ñ
M
enu
Momentarily Display mA Output (HART only)
U
p
RUN Mode
Zero
Adjust Display Decimal
Descriptive Error Message
SENSOR CONFIG Mode
PSIG/BAR (native units)
4-20mA / 20-4mA (HART only)
LRV
URV
Damping
Alarm1
Alarm2
Display Units
Unit Description Scroll
Factory Restore
CALIBRATION Mode
2 Point Cal
4 Point Cal