DryMax MHT100A-1 Посібник користувача - Сторінка 4
Переглянути онлайн або завантажити pdf Посібник користувача для Сушарка DryMax MHT100A-1. DryMax MHT100A-1 12 сторінок. Mht series high inlet temperature refrigerated air dryers
INSTALLATION AND LOCATION
1. Ventilation – Install dryer only in a well-ventilated clean, dry area only and keep at least 3 feet
between the dryer, other equipment and the walls.
2. Dryer Location – Make sure there is approximately 3 feet around the dryer for service and
maintenance purposes. Do not install the dryer outside. The air dryer must not be exposed
to direct sunlight, rain or snow. Do not install the dryer in an environment with fire, high
temperatures or low temperatures.
Make sure the dryer is installed in an environment that is clean and dry. Dust and dirt particles
will clog the air-cooled condenser. A clogged and dirty condenser will reduce the performance
of the dryer and will eventually cause damage to the dryer.
3. Ambient Temperatures – Suitable ambient temperature for the refrigerant dryer is a minimum
of 35 F to a maximum of 110 F. The performance of the dryer will be significantly decreased
when the air dryer is subject to temperatures higher than 110 F. For installations with ambient
temperatures higher than 110 F it is recommended to use a water-cooled condenser on the
dryer. Contact your dealer for details.
4. Selecting Proper In and Out Piping and Piping Design – Pipe diameter should be
sized according to air flow requirements. Do not mix the air inlet and outlet air flow. It
is recommended that a vibration absorber be installed on the dryer inlet and outlet to
eliminate vibration from the compressor. Do not use the inlet and outlet of the air dryer to
support the weight of the air piping.
5. 3 valve bypass and Isolation valves - should be installed on the air dryer outlet and inlet ports
to allow for bypassing, depressurizing, and proper maintenance and servicing of the air dryer.
6. Condensate Drains – Condensate drains must be properly piped from the dryer to prevent
moisture re-entrainment. The dryer is equipped with an automatic drain valve that controls the
discharge of the condensate and a manual valve to manually drain condensate. The user must
run a drain line to an environmentally approved condensate collection/disposal system.
7. Electrical Installation – The dryer data label lists the electrical power requirements for the air
dryer. The user must confirm that the line voltage matches the voltage listed on the data label.
(Warning – Operating the air dryer with improper line voltage will void the warranty.) Provide
the proper size wire, disconnect switches and fuses in accordance with applicable codes. Field
wiring must comply with local and national fire safety and electrical codes. Standard dryer's
enclosures and controls are designed to meet NEMA 1 Type 1 electrical standards. All wiring
is complete. Connect power leads as indicated in the electrical schematic. Ground the frame
properly. Once power is connected turn the power on to the dryer. Leave the power on for 6
hours before you turn the dryer on. This will energize the crank case heater and boil off any
liquid refrigerant in the crank case. Failure to do this may damage the refrigerant compressor
and will void the warranty.
4