Переглянути онлайн або завантажити pdf Дані про встановлення та обслуговування для Аксесуари Daikin McQuay 910113679. Daikin McQuay 910113679 16 сторінок. Digitally adjustable display sensor for water source heat pumps smartsource gs series; smartsource gt series; with microtech iii controls enfinity cch series; enfinity ccw series; enfinity vfc series; enfinity vfw series; enfinity lvc series; enfinity lvw

Daikin McQuay 910113679 Дані про встановлення та обслуговування

Specifications

Supply Voltage:

AC Hot ..................... (R) 7 to 28VAC, 24VAC nominal, 0.17VA
GND/Neutral ...........(5) Sensor common reference ground.

Sensor:

Temperature ............10K-2 Thermistor, ±0.36ºF (±0.2ºC)
Humidity .................2% Accuracy from 20 to 80%,
Capacitive.

Outputs:

Unoccupied .............(U), Unoccupied = Digital low to ground
(Same ground as power source), 100mA
@5VDC max.
Dehumidify .............(DH), = Dehumidify = Voltage output
(same as supply voltage), 170mA max.
System Off ..............(E), System Off = Digital low to ground
(Same ground as power source), 100mA
@5VDC max.
Fan Speed ................(2 or 6), Analog, 0 to 5 VDC.
System Mode ..........(2), Analog, 0 to 5 VDC.
Setpoint ...................(3), Analog, 0 to 5 VDC.
Temperature ............(4), Analog thermistor resistance.

Sensor Controls:

Setpoint ..................2 Up/Down buttons
System .....................1 button to cycle between Heat/Cool
Auto/Off/Dhum/Off
Fan...........................1 button to cycle between Auto/High/On.
Occupied .................1 button to check and request change in
Occupancy Status.
Override/Reset .......1 button to request timed occupancy
override and reset alarms.
Inputs: .....................(1), Controller alarm & system status,
5VDC max.
Termination: ............10 Terminals, 16 to 22 AWG.
Mounting: ................Standard 2" × 4" J-Box or Drywall

Field Setup Jumper J50:

PRG ...........................Program Mode, On = Program, Off = Run.
F/C...........................Display Units, On = ºC, Off = ºF.
MDL ........................MODEL, On = WSHP.

Display:

LCD
Overall size .............2.04"W × 1.33"H.
Main Digits .............±999.9 Digits @0.6"H
Resolution ...............0.5 displayed value, 0.1 for offset adjust
Main Value ..............Temp, Humidity & Setpoint, toggling
every 5 sec.
Eng. Units ...............ºF, ºC, %RH.
System .....................Heat/Cool/Auto/Off/Dhum.
Fan...........................Auto/High/Medium/Low/Off.
Occupied Icon .......... Hollow = Unoccupied, Solid = Occupied.
Function ..................Override, Alarm, E-Save, Setpoint

Field Configuration Menu:

Requires J50 PRG jumper to be "On".
Offset .......................Temp or Humidity display, ±2ºF (±1.0ºC)
and ±5% RH.
Setpoint range .........Default 55º to 95ºF (13º to 35ºC), ±3ºF
(±1.6ºC) or ±5ºF (±3ºC). Adjustable
between 55º to 95ºF, ±3ºF (±1.6ºC) or
±5.0ºF (±2.8ºC).
Fan Lock-in .............Any fan speed or off can be locked in
System Lock-in. Any system mode can
be locked in
Resolution ...............Main display can be default .5, or .1 or
1.0 (ºF, ºC or %).
Display Mode ..........Temp only, RH only, Setpoint only or
any combination.
Dhum DB ..................Dehumidify Dead Band adjust, 2% default.

Enclosure Material:

ABS Plastic, UL94V-0.

Ambient:

32º to 122ºF (0º to 50ºC), 0 to 95%RH, Non-condensing.

Agency:

RoHS.