Wall Mounted
Remove one end cap of the luminaire and insert the required legend.
Access to the mains terminal is achieved by removing one end cap.
Secure the wall bracket to the desired suitable surface (fixings supplied). Bring supply
cable through the centre hole in the wall bracket.
Connect the incoming supply cable to the terminations inside the luminaire ensuring
correct polarity is observed (please see below for electrical connections).
Carefully remove the end cap next to the emergency LED indicator and re-connect the
emergency battery male and female connectors.
Fix the luminaire to the wall bracket from the back of the luminaire housing using the two
fixing screws (supplied).
Electrical Connection
Connect as follows:-
• Make sure the male and female emergency leads are connected.
• Switch on the mains supply. Check the unit operates correctly.
• Check the LED indicator is ON.
• Leave the unit on charge for one hour, then remove the supply to simulate mains failure and check the lamp operates in emergency
mode.
• The unit requires 24 hours to fully charge the battery and achieve 3 hours emergency operation.
Maintenance
Daily :
Monthly :
Bi-Annually:
Annually:
Annually thereafter
If the unit fails to provide the required duration, replace the battery with one that meets the same specification.
Warning
Disconnect the mains supply and unplug the battery leads before working on the unit.
Failure to comply with these instructions may result in irreparable damage to the emergency control gear.
This product must not be modified in any way as this will negate any Safety approvals, and may render the product inoperable or
unsafe. The product must be installed in accordance with the instructions.
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Disposal of Electronic Equipment WEEE Directive 2002/96/EC
This product falls within the scope of the Waste Electrical & Electronic Equipment Directive
(WEEE), which means the product should not be disposed of as normal household waste.
Ensure that this luminaire and lamp is disposed of in accordance with the WEEE Directive.
Contact a local Council Waste Dept. Local Amenity Site, or the Environment Agency for
further information. RoHS - All components and materials used in this product are RoHS
2002/95/EC compliant.
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Page No. 2
®
PERMANENT LIVE
SWITCHED LIVE
NEUTRAL
EARTH
Check LED indicator is illuminated. If the product is maintained check the lamps operate.
Check the unit operates in emergency mode for ¼ of the rated duration.
Check the unit operates of 1 hour for the 3 hour duration.
Check the unit operates for the full 3 hour duration.
Check the unit operates for the full 3 hour duration.
(Lch)
BROWN (continuous)
(Lsw)
BLACK
(N)
BLUE
GREEN / YELLOW