Auber Instruments SYL-2342 Інструкція з експлуатації - Сторінка 2
Переглянути онлайн або завантажити pdf Інструкція з експлуатації для Регулятор температури Auber Instruments SYL-2342. Auber Instruments SYL-2342 8 сторінок. Pid temperature controller
AUBER INSTRUMENTS
3.3 Control output connection
The relay output of the controller SYL-2342 can be used to turn on a contactor
or a solenoid valve. It can drive a small heater directly if the heater draws less
than 10A when connected to 120V AC power source. For applications needing
two control outputs, such as one for heating and another for cooling, relays
AL1 or AL2 can be used for the second output with on/off control mode. Please
see Figure 11 for details.
3.3.1 Connecting the load through a contactor
Assuming the controller is powered by 120V AC and the contactor has a 120V
AC coil, jump a wire between terminals 8 and 9. Connect terminal 7 to one lead
of the coil and terminal 10 to the other lead of the coil. Please see Figure 7 for
example.
3.3.2 Connecting the heater (or cooler) directly from the internal relay
Assuming the controller and the load (heater or cooler) are powered by the
same voltage. Jump a wire from terminal 9 to 8. Connect terminal 7 to the one
lead of the load and terminal 10 to the other lead of the load. Please see Figure
6 and 9 for details.
3.4 For first time users without prior experience with PID controllers, the
following notes may prevent you from making common mistakes.
3.4.1 There is no power that flows through terminal 9 and 10 of the controller to
the heater. This is because this controller consumes less than 2 watts of power,
providing only a control signal to relay. Therefore, wires in the 18 to 26 gauge
range should be used to provide the power for terminals 9 and 10. (Thicker
wires may be more difficult to install)
3.4.2 The alarm relays AL1 and AL2, are "dry" single pole switches, which
means they provide no power to themselves. Please see Figure 6, 7 and 11 for
how they are wired when providing a 120V output (or when output voltage is
the same as the power source for the controller). If the load of the relay
requires a different voltage than that for the controller, another power source
will be needed. See Figure 8 for examples.
3.4.3 For all controller models listed in this manual, the power is modified by
regulating the duration of "on" time for a fixed period. It is not controlled by
regulating amplitude of the voltage or current. This is often referred as time
proportional control. For example, if the cycle rate is set for 100 seconds, a 60%
output means controller will switch on the power for 60 seconds and off for 40
seconds (60/100 = 60%). Almost all high power control systems use time
proportional control because amplitude proportional control is too expensive
and inefficient.
4. Front Panel and Operation
3
4
5
6
Figure 2. Front panel
① PV display: Indicates the sensor's read out or process value (PV).
② SV display: Indicates the set value (SV) or output value (%).
③ AL1 indicator: It lights up when AL1 relay is on. (Display alarm 1)
④ AL2 indicator: It lights up when AL2 relay is on (Display alarm 2).
⑤ A-M indicator: The light indicates that the controller is in manual mode. For
the controllers with the Ramp/Soak option, this light indicates that the
program is running.
⑥ Output indicator: It is synchronized with control output (terminal 7 and 8),
and the power to the load. When it is on, the heater (or cooler) is powered.
2021.06
1
2
7
8
9
10
⑦ SET key: When it is pressed momentarily, the controller will switch the
lower (SV) display between set value and percentage of output. When
pressed and held for two seconds will put the controller into parameter
setting mode.
⑧ Automatic/Manual function key (A/M) /Data shift key.
⑨ Decrement key ▼: Decreases numeric value of the setting value.
⑩ Increment key ▲: Increases numeric value of the setting value.
4.1 Display Status
SET
SET
SET
A/M
2S
SET
Figure 3. Display modes
Display mode 1: When the power is turned on, the upper display window
shows the measured value (PV), and the lower window shows the four-digit set
value (SV).
Display mode 2: Press the SET key to change the display status into mode 2.
The upper display window shows the measured value (PV), and the lower
windows shows the output value. The example above pictures the output
percentage at 60% when in Automatic (PID) control mode. If parameter A-M =
1 (see table 2), pressing the A/M key will switch the controller between PID and
Manual control mode while leaving the output unchanged. This
bumpless/smooth transfer allows the controller to be switched between manual
and automatic mode without the output suddenly "bumping" to a different value.
Display mode 3: Press the SET key for 2 seconds to enter the display mode 3.
(This mode allows users to change the system parameters.)
4.2 Basic Operation
4.2.1 Changing set value (SV)
Press the ▼ or ▲ key once. The decimal point on the lower right corner will
start to flash. Press the ▼ or ▲ key to change SV until the desired value is
displayed. If SV has a large change, press the A/M key to move the flashing
decimal point to the desired digit that needs to be changed. Then press the ▼
or ▲ key to start changing SV from that digit. The decimal point will stop
flashing after no key is pressed for 3 seconds. The changed SV will be
automatically registered without pressing the SET key.
4.2.2 Display change
Press the SET key to change the display mode. The display can be changed
between display modes 1 and 2.
WWW.AUBERINS.COM
A/M
P2/8