needs a controller SYL-5352P, a solid state relay (SSR), a thermocouple and a
two buzzers with a 12V DC power source.
a. Wiring
Alarm1
Alarm2
12V
DC
1
13
14
2
3
SYL-5352P
+
4
-
5
10
TC
Figure 12. Wiring diagram for the oven in example 3.
b. Parameter setting and program
SSb = 5. Safety start band is set to 5 degree.
LOOP = 0. Program automatically looping is disabled.
ALP = 1. Alarm 1 is set to absolute high alarm.
AL1 = 450. Alarm 1 will be activated when reading temperature is over 450
AL2 = 120. Program ending alarm is set to 120s. Once all the steps have been
executed, alarm 2 will be activated for 120s.
The program:
r01 = 2000, t01 = 20, C01 = 375. Heat up to 375 as fast as possible, then soak
at 375 for 20 minutes
r02 = 0, t02 = 0, C02 = 0. End of the program.