Auber Instruments SYL-2362B Інструкція з експлуатації - Сторінка 3
Переглянути онлайн або завантажити pdf Інструкція з експлуатації для Контролер Auber Instruments SYL-2362B. Auber Instruments SYL-2362B 5 сторінок. Pid temperature controller
AUBER INSTRUMENTS
Instruction Manual
4 - Relay J1 as alarm output; J2 as On/off control relay contactor output;
SSR output disabled;
5 - Relay J1 as alarm output; J2 as Limit control relay contactor output;
SSR output disabled;
6 - Relay J1, J2 as alarm output; SSR for Limit control output.
Note 3. Hysteresis Band (also called dead band, or differential), Hy, is used for
On/off control and Limit control. Its unit is in degrees (
control mode, the output will be off when PV>SV and on again when PV <SV-
Hy for heating. For cooling, the output will be off when PV<SV and on again
when PV>SV+Hy. For Limit control mode, the controller can not be reset (to
turn on the output) when PV>SV-Hy for heating, and when PV< SV+Hy f o r
cooling.
Note 4 . The autotune offset will shift the SV value down by the Atdu value
during the autotune process. That will prevent the system from damage due to
overheating during the autotune.
Note 5. Calibration offset, PSb is used to set an input offset to compensate
the error produced by the sensor. For example, if the meter displays 5 ºC
when probe is in ice/water mixture, setting PSb=-5, will make the controller
display 0 ºC. To set negative value, shift to the very left digit, press down key
until it shows "-".
5.2 PID Parameters (accessed by code 0036)
The PID and relevant parameters are listed in table 3. To change the
parameters, press
, enter code "0036", and press
SET
parameter flow chart is similar to Figure 3.
Table 3. PID and relevant parameters
Sy mbol
Description
P
Proportional Constant
P
I
Integral Time
I
d
Deriv ativ e Time
d
SouF
Damp Constant
SouF
ot
Cy cle Rate
ot
FILt
Digital Filter Strength
FILt
End
Ex it
End
The values of the P, I, and D parameters are critical for good response time,
accuracy and stability of the system. Using the Auto-tune function to
automatically determine these parameters is recommended for the first time
user. If the auto-tuning result is not satisfactory, you can manually fine-tune
the PID constants for improved performance.
Note 6. Proportional Constant (P): P is also called the proportional band. Its
unit is the percentage of the temperature range. e. g. For a K type
thermocouple, the control range is 1500 °C. P=5 means the proportional
band is 75 °C (1500x5%). Assuming the set temperature (SV) = 200. When
integral, I, and derivative, d, actions are removed, the controller output power
will change from 100% to 0% when temperature increases from 125 to
200°C. The smaller the P value is, the stronger action will be for the same
temperature difference between SV and PV.
Note 7. Integral time (I): Brings the system up to the set value by adding to
the output that is proportional to how far the process value (PV) is from the
set value (SV) and how long it has been there. When I decreases, the
response speed is faster but the system is less stable. When I increases,
the respond speed is slower, but the system is more stable.
Note 8. Derivative time (d): Responds to the rate of PV change, so that the
controller can compensate in advance before |SV-PV| gets too big. A larger
number increases its action. Setting d-value too small or too large would
decrease system stability, causing oscillation or even non-convergence.
Note 9. Damp constant: This constant can help the PID controller further
improve the control quality. It uses artificial intelligence to dampen the
temperature overshoot. When its value is too low, the system may
overshoot. When its value is too high, the system might be over damped.
2018.07
C or
F). For On/off
°
°
again. The
SET
Setting Range
Initial
Note
0.1~99.9(%)
5.0
6
2~1999(Sec)
100
7
0~399(Sec)
20
8
0.1~1.0
0.2
9
2~199(Sec)
2
10
0~3
0
11
SouF too low
SouF acceptable
Figure 4. Damp constant
Note 10. Cycle rate (ot): It is the time period (in seconds) that the controller
use to calculate its output. e.g. If ot=2, and the controller output is set to 10%,
the heater will be on 0.2 second and off 1.8 seconds for every 2 seconds.
Smaller ot value result in more precision control. For SSR output, ot is
normally set at 2. For relay or contactor output, it should be set longer to
prevent contacts from wearing out too soon. It normally set to 20~40 seconds.
Note 1 1 . Digital Filter (FILt): FILt=0, filter disabled; FILt=1, weak filtering
effect; FILt=3, strongest filtering effect. Stronger filtering increases the stability
of the readout display, but causes more delay in the response to changes in
temperature.
5.3 Temperature setting and Alarm setting (accessed by code 0001)
The temperature and alarm parameters are listed in table 4. To change the
parameters, press
, enter code "0001" an d press
SET
parameter flow chart is similar to Figure 3.
Table 4. Temperature and alarm parameters
Sy mbol
Description
SV
Target temperature(Set Value)
SV
AH1
J1 on temperature
AH1
AL1
J1 off temperature
AL1
AH2
J2 on temperature
AH2
AL2
J2 off temperature
AL2
END
END
Note 12. There are two ways to set the target temperature.
a. During the normal operation mode, press
display from PV to set value. The display will start to blink. Press
again to increase or decrease the SV. When finished, wait 8 seconds and the
settings will take effect automatically (the display will stop blinking).
b. Press
key once. Use
>
SET
key to confirm, then the display would be SV (Su). Press
SET
to display the SV setting. Use
>
and press
to confirm. Press
SET
press
to exit. You can also ignore the steps after confirmation of SV. The
SET
controller will returns to normal operation mode automatically if no key is
pressed for 1 minute.
Note 13. Alarm setting. The J1 relay is controlled by parameters AH1 and
AL1. And the J2 relay is controlled by parameter AH2 and AL2. AH1 (or AL2)
is the temperature to turn the J1 (or J2) relay on; AL1 (or AL2) is the
temperature to turn the J1 (or J2) relay off. When AH1>AL1 (or AH2>AL2), the
J1 (or J2) alarm is set for absolute high alarm as shown in Figure 5 below.
When AH1 <AL1 (or AH2<AL2) , the J1 (or J2) alarm is set for absolute low
alarm as shown in Figure 6 below. When AH1=AL1 (or AH2=AL2), the J1 (or
J2) alarm is deactivated.
Please note that J2 can't be used as alarm when Outy is set to 1, 4 or 5.
PV
AH1
AL1
SV
Relay on
Figure 5. Absolute high alarm
6. Auto-Tuning
The auto-tuning function (also called self tuning) can automatically optimize
the PID parameters for the system. The auto-tuning function will use the On/
off mode to heat up the system until it passes the set point. Then let it cool
down. It will repeat this about three times. Based on the response time of the
WWW.AUBERINS.COM
SouF too high
again. The
SET
Initial Setting
800
800
900
800
900
Ex it
or
once to switch the
,
and
keys to enter code 0001. Press
SET
,
and
keys to enter the new SV value
key to change the display to END. Then,
AL1
AH1
SV
Relay on
Figure 6. Absolute low alarm
Note
12
13
or
key again
PV
P3/5