4.
Adjustments
1
3
Initial Start Voltage
Start Ramp Time
Stop Ramp Time
710-02407-00J
03243.D
Select the initial start voltage (A).
Application
Centrifugal Pump
Submersible Pump
Screw Compressor
Conveyor
Crusher
Fan
Other applications
Select the start ramp time (B).
The start ramp defines how long the soft starter will
take to increase voltage from the initial start voltage to
full voltage.
The start ramp time does not control the time the
motor will take to reach full speed.
1. Set the start ramp time to 20 seconds.
2. Set the initial start voltage as required for the
application.
3. Attach a current monitoring device to output T1.
4. Start the motor under normal load conditions.
Record the time required for the measured current
to fall to (or below) the motor's rated full load
current (t
) then stop the motor.
1
5. Set start ramp time = t
NOTE
The start ramp time must be long enough
for the motor to reach full speed before the
soft starter enters bypass mode.
Select the soft stop ramp time (C).
Soft stop extends the time soft starter takes to reduce
voltage to zero.
The ramp time does not control the time the motor will
take to stop completely.
CSX User Manual
Initial Start Voltage
Start Ramp Time
Stop Ramp Time
Initial Start Voltage -
Suggested setting
50%
60%
70%
.
1
ADJUSTMENTS
7