Elbows
Radius tracks are manufactured to match the radius of the DuctSox. This is typically 1.5 times the
diameter of the DuctSox.
For example, the inside radius track of a 74" diameter DuctSox would have a radius of 79.2".
74" x 1.07 = 79.2"
((74" x 1.5) - (74"/2 x .866) = 79.2")
The center 12:00 radius track would have a radius of 111".
(74" x 1.5 = 111")
And the outside radius track of a 74" diameter DuctSox would have a radius of 142.8".
74" x 1.93 = 142.8"
((74" x 1.5) + (74"/2 x .866) = 142.8")
Install at least one support per radius section, in the center if possible.
Coupler will not go into radius track the full 6" (150mm) and it shouldn't. Coupler must only be inserted
into radius track 1.5" (38mm). This connection will only use one screw in the radius track portion. There
will be 3" (51mm) radius couplers when splicing radius-to-radius connections.
Radius track will only work with DuctSox that are installed in a true horizontal plane (Figure A).
Vertical elbows are supported by D-ring straps rather than radius track (Figure B).
Figure A
Figure B
13
Installation Guide: U-Track