Once the water level reaches the Level Probe again the pump is re-enabled, and so allowed to run.
The solenoid valve will remain open for a further ONE minute before closing. The top-up cycle is now
complete and the green LED changes from flashing to solid.
Self Maintenance: The Control Unit will momentarily open and close the Solenoid Valve three times a
week to prevent blockages. This process takes place automatically.
Safety Shutdown: During a top-up cycle, if the water level in the tank has not reached the level probe
after 30 minutes of topping up, the unit will shut off the pump and close the solenoid. The red alarm
LED lights to indicate that there is one or more of: 1. a leak or blockage in the delivery pipework
feeding to the tank, 2. a failure of the tank itself, or 3. a problem with the solenoid valve.
LED Indicators
Green - Solid
Green - Flashing
Red - Solid
Red - Flashing
TCA5000950 v1.3
Normal Operation. Solenoid Valve closed. Pumps runs as usual.
Water level sufficient.
Top-up cycle in progress. Solenoid Valve open (topping up).
Pump is disabled (switched off) during top-up.
Safety shutdown.
Top up failed.
Control Unit stopped manually
(stop/reset button has been pressed by an operator).