Menu survey
Function
Normal operation
Temperature (setpoint)
Thermostat
Differential
Max. limitation of setpoint setting
Min. limitation of setpoint setting
Adjustment of temperature indication
Temperature unit (°C/°F)
Correction of the signal from S4
Correction of the signal from S3
Manual service, stop regulation, start regulation (-1, 0, 1)
Displacement of reference during night operation
Thermostat function (Read out)
ON/OFF
Definition and weighting, if applicable, of thermostat sensors - S4% (100%=S4, 0%=S3)
Time between melt periods
Duration of melt periods
Temperature setting for thermostat band 2
S6
Correction of the signal from
Definition and weighting, if applicable, of thermostat sensors when night cover is on.
(100%=S4, 0%=S3)
S4 min. limit, Frost protection. Cooling is stopped.
Alarms
Delay for temperature alarm
Delay for door alarm
Delay for temperature alarm after defrost
High alarm limit for thermostat 1
Low alarm limit for thermostat 1
High alarm limit for thermostat 2
Low alarm limit for thermostat 2
High alarm limit for sensor S6 at thermostat 1
Low alarm limit for sensor S6 at thermostat 1
High alarm limit for sensor S6 at thermostat 2
Low alarm limit for sensor S6 at thermostat 2
S6 alarm time delay
With setting = 240 the S6 alarm will be omitted
Alarm time delay or signal on the DI1 input
Alarm time delay or signal on the DI2 input
Signal for alarm thermostat. S4% (100%=S4, 0%=S3)
Delay for S6 (product sensor alarm) after defrost
Alarm limit for max. S7 brine temperature
Differential for S7 brine alarm
Compressor
Min. ON-time
Min. OFF-time
Time delay for cutin of comp.2
Compressor 1 on time when sensor fault (compressor 2 = off )
Compressor 1 off time when sensor fault
Defrost
: 0=none, 1= EL
Defrost method
Defrost stop temperature
Interval between defrost starts
Max. defrost duration
Displacement of time on cutin of defrost at start-up
6
Parameter
. As differential r01 is used
Instructions RI8SE202 © Danfoss 07/2017
EL-diagram
page 1
Min.-
value
Code
1
- - -
1
-50°C
r01
1
0.1 K
r02
1
-49°C
r03
1
-50°C
r04
1
-10
r05
1
0/°C
r09
1
-10 K
r10
1
-10 K
r12
1
-1
r13
1
-50 K
r14
1
—
=On/Off
r15
1
0 %
r16
1
0 hrs
r17
1
0 min.
r21
1
-50°C
r59
1
-10 K
r61
1
0 %
r98
1
-50°C
A03
1
0 min.
A04
1
0 min.
A12
1
0 min.
A13
1
-50°C
A14
1
-50°C
A20
1
-50°C
A21
1
-50°C
A22
1
-50°C
A23
1
-50°C
A24
1
-50°C
A25
1
-50°C
A26
1
0 min.
A27
1
0 min.
A28
1
0 min.
A36
1
0 %
A52
1
0 min.
A76
1
-50°C
A77
1
0.1 K
c01
1
0 min.
c02
1
0 min.
c05
1
0 sec
c86
1
0 min
c87
1
0 min
d01
1
0/No
d02
1
0°C
d03
1
0 hrs/Off
d04
1
0 min.
d05
1
0 min.
SW = 1.0x
Factory
Actual
Max.-value
setting
setting
50°C
2
20 K
2
50°C
50
49°C
-50
10
0
1/F
0/°C
10 K
0
10 K
0
1
0
50 K
0
—
—
100 %
100
10 hrs
1
30 min.
5
50°C
2
10 K
0
100 %
100
20°C
-50°C
240 min.
30
240 min.
60
240 min.
90
50°C
8
50°C
-30
50°C
8
50°C
-30
50°C
8
50°C
-30
50°C
8
50°C
-30
240 min.
240
240 min.
30
240 min.
30
100 %
100
240 min.
90
50°C
8°C
10 K
3.0 K
30 min.
0
30 min.
0
999 sec
5
240 min
15
240 min
15
1/EL
1/EL
50°C
6
240 hrs
8
360 min.
45
240 min.
0
AK-CC 460