Main settings
Measurements
AK error
Comp. Ctrl. temp.
S4 Cold brine supply
S3 Cold brine return
P0 °C
Comp. ctrl. Ref. °C
Compressor cap. %
Request Comp. Cap %
Cond. ctrl. temp °C
S7 warm brine °C
Pc °C
Cond. ctrl. ref. °C
Cond. cap. %
Request Cond. cap %
External Main Switch
Settings
Main switch
Configuration lock
Select quick setup
Refrigerant type Po
Suction capacity control
Measurements
AK error
Comp. Ctrl. temp.
S4 Cold brine supply
S3 Cold brine return
P0 °C
Comp. ctrl. Ref. °C
Compressor cap. %
Request Comp. Cap %
Cond. ctrl. temp °C
S7 warm brine °C
Pc °C
Cond. ctrl. ref. °C
Cond. cap. %
Request Cond. cap %
MC dP0 offset K
S3 offset
Ext. Ref. Offset °C
Night setback
Suction status
4
When "ON", the controller is in alarm condition.
Actual temperature for compressor control
Actual cold brine supply temperature measured with S4 temp. sensor
Actual cold brine return temperature measured with S3 temp. sensor
Suction pressure in °C. (Measured with the pressure transmitter)
Actual reference temperature for compressor control
Cut-in compressor capacity in % (of total capacity)
Reference for compressor capacity (deviations may be due to time delays)
Actual temperature for control sensor (Pc or S7)
Actual warm brine temperature for S7 media sensor
(Only used if S7 sensor is selected as regulation sensor)
Condensing pressure in °C. (measured with the pressure transmitter)
Actual reference temp. for condenser capacity
(incl. external reference signal, if any)
Cut-in condenser capacity in % (of total capacity)
Reference for condenser capacity
Status of input "Extern Main Switch". In pos. "OFF" the regulation is stopped by force
Main switch:
Lock of configuration.
In order to select quick setup or select refrigerant type, the configuration lock must
be "open". Note: "Main switch" must be OFF in order to set configuration lock in "open"
position
0: Open
1: Locked
Select a pre defined application. All in- and outputs will be pre-defined.
All setpoint will be adapted to the selected application. Please notice that the control
ler will make a restart when a selection has been made.
See AK-PC 840 manual for further details about the predefined applications.
Select refrigerant type
0= not selected, 1=R12. 2=R22. 3=R134a. 4=R502. 5=R717. 6=R13. 7=R13b1.
8=R23. 9=R500. 10=R503. 11=R114. 12=R142b. 13=User defined 14=R32. 15=R227.
16=R401A. 17=R507. 18=R402A. 19=R404A. 20=R407C. 21=R407A. 22=R407B.
23=R410A. 24=R170. 25=R290. 26=R600. 27=R600a. 28=R744. 29=R1270. 30=R417A
When "ON", the controller is in alarm condition.
Actual temperature for compressor control
Actual cold brine supply temperature measured with S4 temp. sensor
Actual cold brine return temperature measured with S3 temp. sensor
Suction pressure in °C. (Measured with the pressure transmitter)
Actual reference temperature for compressor control
Cut-in compressor capacity in % (of total capacity)
Reference for compressor capacity (deviations may be due to time delays)
Actual temperature for control sensor (Pc or S7)
Actual warm brine temperature for S7 media sensor
(Only used if S7 sensor is selected as regulation sensor)
Condensing pressure in °C. (measured with the pressure transmitter)
Actual reference temp. for condenser capacity
(incl. external reference signal, if any)
Cut-in condenser capacity in % (of total capacity)
Reference for condenser capacity
Actual displacement value for the suction pressure in connection with a "P0
Optimiser" function (Master control function in AKA gateway)
Contribution from reference displacement via S3 sensor
Contribution from external reference displacement
Status of night setback function
ON: Night (An increase of the evaporating pressure is permitted)
OFF: Normal situation
0: Power up Controller has been powered up (power supply re-connected)
1: Stopped
Service Guide
RC8BV402 © Danfoss 2016-02
ON:
Regulation
OFF: Controller stopped
Capacity control has been stopped ("Main switch" = OFF or
"Control mode" = OFF)
AK-CH 650 Version 2.0x