3S TE200 Інструкція з експлуатації - Сторінка 12

Переглянути онлайн або завантажити pdf Інструкція з експлуатації для Конвертер мультимедіа 3S TE200. 3S TE200 20 сторінок.

3-3-2 Electrical Installation

(1) Flame-proof version

When performing electrical installation, never remove the terminal box cover or
attempt to connect the wiring while the electrical power is still connected. (Similarly,
do not open the main cover.)
① Cabling
Use insulated cables able to withstand temperatures of 75[deg]C or higher for the
external cabling.
② External conductor cabling
The following two methods can be used for conductor cabling on the Flame-proof version
(Ex d IIB T6).
Cable pipe with threaded pressure coupling method
Use a G1/2 thick steel cable pipe (PF1/2 equivalent) with a lock nut to provide a full
threaded coupling. Alternatively, use a sealing fitting.
Pressure-proof packing method
Use a cable gland.
The table below lists the applicable cable diameters.
Cable glands with the part numbers listed below are available as optional extras. Please
specify when ordering.
Model
Standard
TE15●
Ex d IIB T6
*
Please contact us for NPT specification.
Applicable Cable
Rating Number
TC13351
Cable Gland Part No.
Diameters
φ8~φ10
KHB-0-16/PK1610
φ9~φ11
KHB-0-16/PK1611
φ10~φ12
KHB-0-16/PK1612
3-3