7.0
System Tests
7.1
Input the times from this table to ensure Smart -Vent is working correctly. Replace the outside temperature
sensor with a potentiometer to simulate outside air temperature.
(NOTE: Smart-Vent should be to powered off during air sensor change-over).
7.2
Adjust the following settings to carry out the required test:
OAT
PP
DTFC
NTFC
CO₂
SETPOINT
Test
Time
05:28
Pre-Purge
05:32
05:45
05:45
06:15
DTFC
06:15
06:15
17:15
18:15
NTFC
18:15
18:15
06:15
CO₂
06:15
05:32
06:15
OAT
18:15
06:15
Note:
i)
Where the OAT is Low it requires to be less than 10°C
Tests above assume day time (occupied) times are 06:00 – 18:00, adjust to suite timeclock schedule
ii)
iii)
Reconnect outside air sensor when tests are complete
iv)
Return timeclock schedule to its desired settings
SPARES/SERVICE
PLEASE WRITE THE DETAILS OF THE UNIT HERE.
These details will be required when ordering spares for you Dunham-Bush Smart-Vector network panel
UNIT TYPE AND MODEL INFORMATION
SERIAL NUMBER
DATE OF INSTALLATION
Spare parts/service – Please contact our office, contact information shown on page 1
Manufacturer reserves the right to change any product specification without notice
Outside Air Temperature; adjust using the potentiometer
Pre-Purge; enabled using the switch
Daytime Free-Cooling; enabled using the switch
Night-time Free-Cooling; enabled using the switch
Use a CO₂ spray or breathe on the sensor on Smart-Vector room controller
Adjust on the Smart Vector Controller
OAT
Pre-Purge
DTFC
MID
ON
OFF
MID
ON
OFF
MID
OFF
OFF
MID
OFF
ON
MID
OFF
ON
MID
OFF
OFF
MID
OFF
ON
MID
OFF
OFF
MID
OFF
OFF
MID
OFF
OFF
MID
OFF
OFF
MID
OFF
OFF
MID
OFF
OFF
LOW
ON
ON
LOW
ON
ON
LOW
ON
ON
LOW
ON
ON
SETTINGS
NTFC
CO₂
OFF
LOW
OFF
LOW
OFF
LOW
OFF
LOW
OFF
LOW
OFF
LOW
OFF
LOW
ON
LOW
ON
LOW
OFF
LOW
ON
LOW
OFF
LOW
OFF
HIGH
ON
LOW
ON
LOW
ON
LOW
ON
HIGH
Expected Results
SETPOINT
Fan(s)
MID
OFF
MID
ON
MID
OFF
LOW
OFF
LOW
ON
LOW
OFF
HIGH
OFF
LOW
OFF
LOW
ON
LOW
OFF
HIGH
OFF
MID
OFF
MID
ON
MID
OFF
MID
OFF
MID
OFF
MID
ON
Damper
CLOSED
OPEN
CLOSED
CLOSED
OPEN
CLOSED
CLOSED
CLOSED
OPEN
CLOSED
CLOSED
CLOSED
OPEN
CLOSED
CLOSED
CLOSED
OPEN
Page 8 of 8