In-bottom/Out-back Cooling Kit for FA11-FA12
Installation Guide
6X S-M10-2Z1
3 (0.1)
Illustration 5: Vent Dimensions for FA12 Mounting Plate in 800 mm (32 in) Cabinet
2.4 Creating Vent Opening in the Backplate
To create a vent opening in the cabinet backplate, use the following steps. Use the dimensions in
cabinets, and
Illustration 7
for 800 mm (32 in) cabinets.
Procedure
1.
Cut out the vent opening in the cabinet backplate using the template dimensions.
The opening must match the frequency converter vent opening.
2.
Drill 8 screw holes (6 mm) around the vent opening using the template dimensions.
The holes must match the holes in the outer flange of the back duct.
Danfoss A/S © 2022.12
7 (0.3)
699 (27.5)
Installation
23 (0.9)
0.0
100 (3.9)
2X 137 (5.3)
158 (6.2)
169 (6.7)
314 (12.3)
326 (12.8)
2X 347 (13.7)
1645 (64.7)
Illustration 6
for 600 mm (24 in)